11-12
Front-Panel Interface
Date Code 20010625
SEL-311L Instruction Manual
The following table and figures demonstrate the correspondence between changing display point
states (e.g., DP2 and DP3) and enabled display point labels (DP2_1/DP2_0 and DP3_1/DP3_0,
respectively). The display time is equal to global setting SCROLD for each screen.
The display point example settings are:
DP2 = CHXAL
(alarm condition on Channel X)
DP3 = CHYAL
(alarm condition on Channel Y)
Display Points 2 and 3 are used to help diagnostics when the 87CH FAIL LED illuminates.
Display Points
(SEL
OGIC
Control
Equation
Settings)
Example
Display
Point States
Display Point
Label Settings
DP2 = CHXAL
DP3 = CHYAL
= logical 0
= logical 0
DP2_1 = CHANNEL X ALARM
DP2_0 = NA
DP3_1 = CHANNEL Y ALARM
DP3_0 = NA
':*0/
DP2 = CHXAL
DP3 = CHYAL
= logical 1
= logical 0
DP2_1 = CHANNEL X ALARM
DP2_0 = NA
DP3_1 = CHANNEL Y ALARM
DP3_0 = NA
':*0/
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......