G-4
Setting SEL
OGIC
®
Control Equations
Date Code 20010625
SEL-311L Instruction Manual
SEL
OGIC
Control Equation Parentheses Operator ( )
More than one set of parentheses ( ) can be used in a SEL
OGIC
control equation setting. For
example, the following SEL
OGIC
control equation setting has two sets of parentheses:
SV7 = (SV7+IN101) * (50P1+50G1)
In the above example, the logic within the parentheses is processed first and then the two
parentheses resultants are ANDed together. Parentheses cannot be “nested” (parentheses within
parentheses) in a SEL
OGIC
control equation setting.
SEL
OGIC
Control Equation NOT Operator !
The NOT operator ! is applied to a single Relay Word bit and also to multiple elements (within
parentheses). Following are examples of both.
Example of NOT Operator ! Applied to Single Element
The internal circuit breaker status logic in the
SEL-
311L Relay operates on 52a circuit breaker
auxiliary contact logic. The SEL
OGIC
control equation circuit breaker status setting is labeled
52A. See
Optoisolated Inputs
in
Section 7: Inputs, Outputs, Timers, and Other Control Logic
and
Close Logic
in
Section 6: Close and Reclose Logic
for more information on SEL
OGIC
control equation circuit breaker status setting 52A.
When a circuit breaker is closed, the 52a circuit breaker auxiliary contact is closed. When a
circuit breaker is open, the 52a contact is open.
The opposite is true for a 52b circuit breaker auxiliary contact. When a circuit breaker is closed,
the 52b circuit breaker auxiliary contact is open. When the circuit breaker is open, the 52b
contact is closed.
If a 52a contact is connected to optoisolated input IN101, the SEL
OGIC
control equation circuit
breaker status setting 52A is set:
52A = IN101
Conversely, if a 52b contact is connected to optoisolated input IN101, the SEL
OGIC
control
equation circuit breaker status setting 52A is set:
52A = !IN101
[= NOT(IN101)]
With a 52b contact connected, if the circuit breaker is closed, the 52b contact is open and input
IN101 is deenergized [IN101 = 0 (logical 0)]:
52A = !IN101 = NOT(IN101) = NOT(0) = 1
Thus, the SEL
OGIC
control equation circuit breaker status setting 52A sees a closed circuit
breaker.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......