3-62
Line Current Differential, Distance, Out-of-Step, Overcurrent,
Date Code 20011112
Voltage, Synchronism Check, and Frequency Elements
SEL-311L Instruction Manual
Figure 3.47: Phase Time-Overcurrent Element 51PT
Accuracy
Pickup:
±
0.05 A secondary and
±
3% of setting (5 A nominal phase current inputs, IA, IB, IC)
±
0.01 A secondary and
±
3% of setting (1 A nominal phase current inputs, IA, IB, IC)
Curve Timing:
±
1.50 cycles and
±
4% of curve time for currents between (and including)
2 and 30 multiples of pickup
51PT Element Logic Outputs
The logic outputs in Figure 3.47 are the Relay Word bits shown in Table 3.8.