Date Code 20010625
Trip and Target Logic
5-25
SEL-311L Instruction Manual
As explained in the preceding POTT subsection, the SEL
OGIC
control equation settings PT1 and
PT2 in Figure 5.7 are routed in various combinations to control Relay Word bit PT, depending
on enable setting ECOMM = DCUB1 or DCUB2. Relay Word bit PT is then an input into the
POTT logic in Figure 5.8 (for echo keying).
LOG1, LOG2—Loss-of-Guard Signal(s)
In two-terminal line DCUB applications (setting ECOMM = DCUB1), a loss-of-guard signal is
received from one remote terminal. One optoisolated input on the SEL-311L Relay (e.g., input
IN105) is driven by a communications equipment receiver output (see Figure 5.14). Make
SEL
OGIC
control equation setting LOG1:
LOG1 = IN105
(two-terminal line application)
In three-terminal line DCUB applications (setting ECOMM = DCUB2), loss-of-guard signals are
received from two remote terminals. Two optoisolated inputs on the SEL-311L Relay (e.g.,
input IN105 and IN103) are driven by communications equipment receiver outputs (see
Figure 5.15). Make SEL
OGIC
control equation settings LOG1 and LOG2 as follows:
LOG1 = IN105
(three-terminal line application)
LOG2 = IN103
SEL
OGIC
control equation settings LOG1 and LOG2 are routed into the DCUB logic in
Figure 5.12 for “unblocking block” and “permissive trip receive” logic decisions.
Timer Settings
See
Section 9: Setting the Relay
for setting ranges.
GARD1D—Guard-Present Delay
Sets minimum time requirement for reinstating permissive tripping following a loss-of-channel
condition—typically set at 10 cycles. Channel 1 and 2 logic use separate timers but have this
same delay setting.
UBDURD—DCUB Disable Delay
Prevents tripping by POTT logic after a settable time following a loss-of-channel condition—
typically set at 9 cycles (150 ms). Channel 1 and 2 logic use separate timers but have this same
delay setting.
UBEND—DCUB Duration Delay
Sets minimum time required to declare a loss-of-channel condition—typically set at 0.5 cycles.
Channel 1 and 2 logic use separate timers but have this same delay setting.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......