Date Code 20010625
Close and Reclose Logic
6-27
SEL-311L Instruction Manual
Figure 6.7: Sequence Coordination Between the SEL-311L Relay and a Line Recloser
Assume that the line recloser is set to operate twice on the fast curve and then twice on the slow
curve. The slow curve is allowed to operate after two fast curve operations because the fast
curves are then inoperative for tripping. The SEL-311L Relay instantaneous/definite time-
overcurrent element T50PT is coordinated with the line recloser fast curve. The SEL-311L
Relay tapped load phase time-overcurrent element T51PT is coordinated with the line recloser
slow curve.