Date Code 20010625
Inputs, Outputs, Timers, and Other Control Logic
7-3
SEL-311L Instruction Manual
Input Functions
There are
no
optoisolated input settings such as:
IN101
=
IN102
=
Relay Word bits IN101 through IN106, used in SEL
OGIC
control equations, represent the state of
optoisolated inputs IN101 through IN106.
Settings Example 1
Figure 7.2: Circuit Breaker Auxiliary Contact and Reclose Enable Switch Connected to
Optoisolated Inputs IN101 and IN102
The functions for inputs IN101 and IN102 (Figure 7.2) are described in the following
discussions.
Input IN101
Relay Word bit IN101 (Figure 7.2) is used in the settings for the SEL
OGIC
control equation
circuit breaker status setting:
52A = IN101
Connect input IN101 to a 52a circuit breaker auxiliary contact.
If a 52b circuit breaker auxiliary contact is connected to input IN101, the setting is changed to:
52A = !IN101
[!IN101 = NOT(IN101)]
See
Close Logic
in
Section 6: Close and Reclose Logic
for more information on SEL
OGIC
control equation setting 52A.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......