8-26
Breaker Monitor and Metering Functions
Date Code 20010625
SEL-311L Instruction Manual
Time = 10 Minutes
The three 5-minute intervals in the sliding time-window at “Time = 10 minutes” each integrate
into the following 5-minute totals:
5-Minute Totals
Corresponding
5-Minute Interval
0.0 per unit
-5 to 0 minutes
1.0 per unit
0 to 5 minutes
1.0 per unit
5 to 10 minutes
2.0 per unit
Rolling demand meter response at “Time = 10 minutes” = 2.0/3 = 0.67 per unit
Time = 15 Minutes
The three 5-minute intervals in the sliding time-window at “Time = 15 minutes” each integrate
into the following 5-minute totals:
5-Minute Totals
Corresponding
5-Minute Interval
1.0 per unit
0 to 5 minutes
1.0 per unit
5 to 10 minutes
1.0 per unit
10 to 15 minutes
3.0 per unit
Rolling demand meter response at “Time = 15 minutes” = 3.0/3 = 1.0 per unit
Demand Meter Settings
Enable Demand Meter (EDEM) is not visible in application settings 87L, 87L21 and 87L21P.
Table 8.3: Demand Meter Settings and Settings Range
Setting Definition
Range
EDEM
Demand meter type
THM = thermal
ROL = rolling
DMTC
Demand meter time constant
5, 10, 15, 30, or 60 minutes
PDEMP
Phase demand current pickup
OFF
GDEMP
Residual ground demand current pickup
0.10–3.20 A {1 A nominal}
0.50–16.0 A {5 A nominal}
QDEMP
Negative-sequence demand current pickup in 0.01 A steps
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......