7.40
SEL-351A Relay
Instruction Manual
Date Code 20080213
Inputs, Outputs, Timers, and Other Control Logic
Rotating Default Display (Only on Models With LCD)
Displaying Values
(Other Than User-
Entered Text) on the
Rotating Default
Display
through
list all the available values (other than the user-
entered text values, discussed previously) that rotate on the default display,
subject to the number of available display points. These available values cover
metering (
), breaker wear monitor (
), and time-overcurrent
element pickups (
and
).
In general, any of these values can be selected for the rotating default display
with a leading two-character sequence:
::
(double colon)
followed by the mnemonic text setting. For example, to display peak demand
currents (
) for currents IA, IB, IC, and IN, make the following text
(
SET T
command) and logic (
SET L
command) settings:
Logic settings DP1–DP4 are permanently set to logical 0 in this example. This
causes the corresponding DP
n
_0 value to permanently rotate in the display
(the mnemonics in the DP
n
_0 settings indicate the value displayed, per
):
then,
The
Rotating Default Display on page 11.12
explains pictorially which
display setting is displayed (DP
n
_0 or DP
n
_1), depending on the logic state
(logical 0 or 1) of corresponding logic setting DP
n
.
Values Displayed for Incorrect Settings
If the display point setting does not match the correct format (using the
leading two-character sequence
::
followed by the correct mnemonic), the
relay will display the setting text string as it was actually entered, without
substituting the display value. For example:
Again, logic settings DP1 and DP2 are permanently set to logical 0. This
causes the corresponding DP
n
_0 value to permanently rotate in the display.
With the DP
n
_0 setting problems just discussed, the relay displays the setting
text string as it was actually entered, without substituting the intended display
value from
:
SET T
SET L
DP1_0 = ::IAPK
DP1 = 0
DP2_0 = ::IBPK
DP2 = 0
DP3_0 = ::ICPK
DP3 = 0
DP4_0 = ::INPK
DP4 = 0
IA PEAK = 603.5
IB PEAK = 598.7
IC PEAK = 605.1
IN PEAK = 88.2
SET T
SET L
DP1_0 = :IAPK (missing
:
)
DP1 = 0
DP2_0 = ::IBPJ (misspelled mnemonic)
DP2 = 0
Summary of Contents for SEL-351A
Page 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...