Instruction Manual
SEL-351A-1 Relay
SET.7
of 26
SEL-351A-1 Settings Sheets
Relay Settings (Serial Port Command SET and Front Panel)
Negative-sequence (V2) overvoltage pickup
(OFF, 0.00–120.00 V secondary)
59Q2P
=
Positive-sequence (V1) overvoltage pickup
(OFF, 0.00–170.00 V secondary)
59V1P
=
Phase-to-phase undervoltage pickup
(OFF, 0.00–300.00 V secondary)
27PP
=
Phase-to-phase undervoltage pickup
(OFF, 0.00–300.00 V secondary)
27PP2P
=
Phase-to-phase overvoltage pickup
(OFF, 0.00–300.00 V secondary)
59PP
=
Phase-to-phase overvoltage pickup
(OFF, 0.00–300.00 V secondary)
59PP2P
=
Frequency Element (See
–
(Make the following settings if preceding enable setting E81 = 1–3.)
Phase undervoltage block (25.00–300.00 V secondary)
27B81P
=
Level 1 pickup (OFF, 40.10–65.00 Hz)
81D1P
=
Level 1 time delay (2.00–16000.00 cycles in 0.25-cycle steps)
81D1D
=
Level 2 pickup (OFF, 40.10–65.00 Hz)
81D2P
=
Level 2 time delay (2.00–16000.00 cycles in 0.25-cycle steps)
81D2D
=
Level 3 pickup (OFF, 40.10–65.00 Hz)
81D3P
=
Level 3 time delay (2.00–16000.00 cycles in 0.25-cycle steps)
81D3D
=
Reclosing Relay (See
and
)
(Make the following settings if preceding enable setting E79 = 1–4 or C1–C4.)
Open interval 1 time
(0.00–999999.00 cycles in 0.25-cycle steps)
79OI1
=
Open interval 2 time
(0.00–999999.00 cycles in 0.25-cycle steps)
79OI2
=
Open interval 3 time
(0.00–999999.00 cycles in 0.25-cycle steps)
79OI3
=
Open interval 4 time
(0.00–999999.00 cycles in 0.25-cycle steps)
79OI4
=
Reset time from reclose cycle
(0.00–999999.00 cycles in 0.25-cycle steps)
79RSD
=
Reset time from lockout
(0.00–999999.00 cycles in 0.25-cycle steps)
79RSLD
=
Reclose supervision time limit
(OFF, 0.00–999999.00 cycles in 0.25-cycle steps) (set
79CLSD = 0.00 for most applications; see
)
79CLSD
=
Summary of Contents for SEL-351A
Page 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...