12.2
SEL-351A Relay
Instruction Manual
Date Code 20080213
Standard Event Reports and SER
Standard 15/30-Cycle Event Reports
Standard 15/30-Cycle Event Reports
NOTE:
is on multiple
pages.
for an example event report.
Event Report Length
(Settings LER and
PRE)
The SEL-351A provides user-programmable event report length and prefault
length. Event report length is either 15 or 30 cycles. Prefault length ranges
from 1 to 29 cycles. Prefault length is the first part of the event report that
precedes the event report triggering point.
Set the event report length with the LER setting. Set the prefault length with
the PRE setting. See the
SET G
command in
and corresponding
Event Report Parameters (See Section 12) on page SET.20
for instructions on
setting the LER and PRE settings.
Changing the LER setting will erase all events stored in nonvolatile memory.
Changing the PRE setting has no effect on the nonvolatile reports.
Standard Event
Report Triggering
The relay triggers (generates) a standard event report when any of the
following occurs:
➤
Relay Word bit TRIP asserts
➤
Programmable SEL
OGIC®
control equation setting ER asserts
to logical 1
➤
TRI
(Trigger Event Reports) serial port command executed
➤
Output contacts
OUT101
–
OUT107
pulsed via the serial port or
front-panel
PUL
(Pulse Output Contact) command
Relay Word Bit TRIP
. If Relay Word bit TRIP asserts to logical 1, an event
report is automatically generated. Thus, any condition that causes a trip does
not have to be entered in SEL
OGIC
control equation setting ER.
For example, SEL
OGIC
control equation trip setting TR is unsupervised. Any
trip condition that asserts in setting TR causes the TRIP Relay Word bit to
assert immediately. The factory setting for trip setting TR is:
TR =
OC + 51PT + 51GT + 81D1T + LB3 + 50P1 * SH0
If any of the individual conditions 51PT, 51GT, 81D1T, LB3, or 50P1 * SH0
assert, Relay Word bit TRIP asserts, and an event report is automatically
generated. Thus, these conditions do not have to be entered in SEL
OGIC
control equation setting ER.
Relay Word bit TRIP (in
) is usually assigned to an output contact
for tripping a circuit breaker (e.g., SEL
OGIC
control equation setting OUT101
= TRIP).
Summary of Contents for SEL-351A
Page 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...