2.14
SEL-351A Relay
Instruction Manual
Date Code 20080213
Installation
Making Rear-Panel Connections
Models 0351A10
Note the signal labels (
VA
,
VB
,
VC
,
N
) on terminals
Z09
–
Z12
.
shows
the internal connection for terminals
VA
,
VB
,
VC
, and
N
.
Voltage Input Rating
The serial number sticker on the relay rear panel indicates the continuous
voltage input rating, which is 300 Vac for the SEL-351A.
This voltage rating applies to the three-phase voltage inputs (
VA-N
,
VB-N
,
VC-N
)
as well as to the
VS-NS
voltage input, when present. The voltage rating is in
units of V
LN
when the relay is wye connected (three-phase, four-wire), or V
LL
when the relay is delta connected (three-phase, three-wire). The following two
subsections explain the wye and delta voltage input connections.
The part number sticker on SEL-351A relays manufactured with firmware
revision R105 (or higher) indicates “300 V Wye/Delta.” The part number
sticker on previously manufactured SEL-351A relays indicates “300 V Wye.”
If older SEL-351A relays (with firmware revisions R101–R104) are upgraded
to R105 (or higher) firmware, they too can be wye connected or delta
connected, provided that the voltage rating is not exceeded.
Wye-Connected Voltages (Global setting PTCONN = WYE)
Any of the single-phase voltage inputs (i.e.,
VA-N
,
VB-N
,
VC-N
, or
VS-NS
) can be
connected to voltages up to 300 V continuous.
–
and
–
show examples of wye-connected voltages. System
frequency is determined from voltage connected to voltage input
VA-N
.
Additionally, voltage input
VS-NS
measures frequency on the other side of an
open breaker for synchronism check applications. See subsections
Synchronism Check Elements (Not in SEL-351A-1) on page 3.36
and
Frequency Elements on page 3.49
Delta-Connected Voltages (Global setting PTCONN = DELTA)
SEL-351A relays with firmware revision R105 (or higher) can be configured
via Global setting PTCONN = DELTA to accept an open-delta PT connection.
Phase-to-phase voltage up to 300 V continuous can be connected to the relay
when it is connected as shown in
. This connection
requires an external jumper between
VB
(terminal
Z10
) and
N
(terminal
Z12
).
In this configuration, the relay cannot measure zero-sequence voltage (3V
0
)
because the open-delta connection blocks zero-sequence voltage information.
Relay functions that require 3V
0
voltage may be disabled, unless another 3V
0
voltage source is supplied to the relay via voltage input
VS-NS
(see
Delta VS Connection (Global setting VSCONN = 3V0) on page 2.15
).
Referring to
and
, when global setting PTCONN =
DELTA, the relay interprets the voltage signal detected across voltage input
VA-N
as V
AB
, and the voltage signal detected across voltage input
VC-N
as V
CB
(or –V
BC
). Phase-to-phase voltage V
CA
is derived internally (V
CA
= V
CB
–
V
AB
). The relay does not use the voltage signal detected across voltage input
VB-N
, which should effectively be zero due to the jumper between
VB
and
N
.
Unfiltered (raw) event reports are the only means by which signals applied to
relay voltage terminals
VA-N
,
VB-N
, and
VC-N
can be directly observed. See
Unfiltered Event Reports With PTCONN = DELTA on page 12.9
.
Summary of Contents for SEL-351A
Page 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...