5.7
Date Code 20080213
Instruction Manual
SEL-351A Relay
Trip and Target Logic
Switch-Onto-Fault (SOTF) Trip Logic
Switch-Onto-Fault (SOTF) Trip Logic
Switch-Onto-Fault (SOTF) trip logic provides a programmable time window
for selected elements to trip right after the circuit breaker closes. “Switch-
onto-fault” implies that a circuit breaker is closed into an existing fault
condition. For example, suppose safety grounds are accidentally left attached
to a line after a clearance. If the circuit breaker is closed into such a condition,
the resulting fault needs to be cleared right away and reclosing blocked. An
instantaneous overcurrent element is usually set to trip in the three-pole open
(3PO) logic and the SOTF trip logic.
Refer to the switch-onto-fault trip logic in
(top of figure). The
SOTF trip logic permits tripping if
both
the following occur:
➤
An element asserts in SEL
OGIC
control equation trip setting
TRSOTF
➤
Relay Word bit SOTFE is asserted to logical 1
Relay Word bit SOTFE (the output of the SOTF logic) provides the effective
time window for an element in trip setting TRSOTF (e.g., TRSOTF = 50P2) to
trip after the circuit breaker closes.
and the following discussion
describe the three-pole open (3PO) logic and the SOTF logic.
q
;
w
Figure 5.3
Three-Pole Open Logic (Top) and Switch-Onto-Fault Logic (Bottom)
Setting
52A
to LOP Logic
q
3PO
50L
50LP
Monitor DC Close Bus
Rising-Edge
Detect
to Trip
Logic
w
SOTFE
Settings
52AEND = OFF
CLMON
CLOEND = OFF
52AEND
SOTFD
CLOEND
0
0
3P0D
0
SOTFD
SEL
OGIC
Setting
SEL
OGIC
Setting
I
A
I
B
I
C
Relay
Word
Bits
Summary of Contents for SEL-351A
Page 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...