6.3
Date Code 20080213
Instruction Manual
SEL-351A Relay
Close and Reclose Logic
Close Logic
Relay Word bit CC asserts for execution of the
CLOSE
command. See
Command (Close Breaker) on page 10.34
for more information on the
CLOSE
command. More discussion follows later on the factory settings for
setting CL.
If a user wants to supervise the
CLOSE
command with optoisolated input
IN106
, the following setting is made:
CL =
… + CC * IN106
With this setting, the
CLOSE
command can provide a close only if
optoisolated input
IN106
is asserted. This is just one
CLOSE
command
supervision example—many variations are possible.
Unlatch Close
If the CLOSE Relay Word bit is asserted at logical 1, it stays asserted at
logical 1 until one of the following occurs:
➤
The unlatch close condition asserts (ULCL = logical 1).
➤
The circuit breaker closes (52A = logical 1).
➤
The reclose initiation condition (79RI) makes a rising-edge
(logical 0 to logical 1) transition.
➤
Or the Close Failure Timer times out (Relay Word bit CF = 1).
The Close Failure Timer is inoperative if setting CFD = OFF.
Factory Settings
Example
The factory settings for the close logic SEL
OGIC
control equation settings are:
52A =
IN101
CL =
LB4 + CC
ULCL =
TRIP
The factory setting for the Close Failure Timer setting is:
CFD =
60.00 cycles
See the
Settings Sheets
at the end of
for settings
ranges.
Set Close
If the Reclosing Relay Open Interval Time-Out logic input at the top of
is ignored (reclosing is discussed in detail in a following
subsection), then SEL
OGIC
control equation setting CL is the only logic input
that can set the CLOSE Relay Word bit.
In SELOGIC control equation setting
CL =
LB4 + CC
➤
Local bit LB4 operates as a manual close switch via the front
panel (only on models with LCD). See
(Only on Models With LCD) on page 7.5
for more information on local control.
➤
Relay Word bit CC asserts for execution of the
CLOSE
command. See
CLO Command (Close Breaker) on page 10.34
for more information on the
CLOSE
command.
Summary of Contents for SEL-351A
Page 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...