6.17
Date Code 20080213
Instruction Manual
SEL-351A Relay
Close and Reclose Logic
Reclosing Relay
79OI2 =
600.00
79OI3 =
0.00
For this example:
Number of reclosures (last shot) = 2 = the number of set open interval
times that precede the first open interval set to zero.
Observe Shot Counter Operation (Only on Models With LCD)
Observe the reclosing relay shot counter operation, especially during testing,
with the front-panel shot counter screen (accessed via the
{OTHER}
Functions Unique to the Front-Panel Interface on page 11.6
Reset Timer
The reset timer qualifies circuit breaker closure before taking the relay to the
Reset State from the Reclose Cycle State or the Lockout State. Circuit breaker
status is determined by the SEL
OGIC
control equation setting 52A. (See
for more discussion on SEL
OGIC
control equation setting
52A. Also see
Optoisolated Inputs on page 7.2
for more discussion on
SEL
OGIC
control equation setting 52A.)
Setting 79RSD
Qualifies closures when the relay is in the Reclose Cycle State. These closures
are usually automatic reclosures resulting from open interval time-out.
It is also the reset time used in sequence coordination schemes [see
Coordination Setting (79SEQ) on page 6.26
].
Setting 79RSLD
Qualifies closures when the relay is in the Lockout State. These closures are
usually manual closures. These manual closures can originate external to the
relay, via the
CLOSE
command, or via the SEL
OGIC
control equation setting
CL (see
Setting 79RSLD is also the reset timer used when the relay powers up, has
individual settings changed for the active setting group, or the active setting
group is changed (see
Reclosing Relay States and Settings/Setting Group
Typically, setting 79RSLD is set less than setting 79RSD. Setting 79RSLD
emulates reclosing relays with motor-driven timers that have a relatively short
reset time from the lockout position to the reset position.
The 79RSD and 79RSLD settings are set independently (setting 79RSLD can
even be set greater than setting 79RSD, if desired). SEL
OGIC
control equation
setting 79BRS (block reset timing) can be set to control reset timing [see
Block Reset Timing Setting (79BRS) on page 6.25
Monitoring Open Interval and Reset Timing
Open interval and reset timing can be monitored with the following Relay
Word bits:
Summary of Contents for SEL-351A
Page 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...