9.37
Date Code 20080213
Instruction Manual
SEL-351A Relay
Setting the Relay
Settings Explanations
Voltage Input Configuration (See Settings for Voltage Input
Configuration on page 9.36) on page SET.20
.
VSCONN = VS
is the factory default value, which leaves voltage input
VS
in its
traditional role of voltage input for the synchronism check elements. See
Synchronism Check Elements (Not in SEL-351A-1) on page 3.36
. VSCONN =
3V0, if selected, allows an external 3V
0
zero-sequence voltage source to be
connected to relay voltage input
VS
. See
Broken-Delta VS Connection (Global
setting VSCONN = 3V0) on page 2.15
. When VSCONN = 3V0, the measured
value from relay voltage input
VS-NS
is used in certain relay elements, as
. When VSCONN = 3V0, some relay
elements are unavailable or cannot be selected. This instruction manual
explains these differences in relation to each affected element or setting. To
indicate the state of VSCONN in SEL
OGIC
control equations, Relay Word bit
3V0 operates as shown in
Voltage Input Configuration (See Settings for Voltage Input
Configuration on page 9.36) on page SET.20
.
VNOM = 67.00 V secondary (when PTCONN = WYE) or 116.05 V secondary
(when PTCONN = DELTA)
is the factory default value. See
Transformer Ratios and PT Nominal Secondary Voltage Settings on page 9.39
for details on using VNOM with numeric setting values. VNOM = OFF, if
selected, causes several relay elements and functions to be disabled or
nonselectable, as shown in
. The relay interprets setting VNOM =
OFF as indicating that valid three-phase voltages are not connected to relay
terminals
VA
,
VB
,
VC
, and
N
. See
for an example application that
uses VNOM = OFF. This selection is intended to allow the remaining relay
features to be used with just one phase voltage connected, without any of the
sequence-voltage-based elements misoperating because of erroneous
quantities.
Table 9.7
Main Relay Functions That Change With VSCONN,
When PTCONN = WYE
Relay Function
When VSCONN=VS
When VSCONN=3V0
Zero-sequence
voltage-polarized ground
directional elements
(ORDER setting choices
“V,” “S,” and “U”)
Uses 3V
0
calculated
from V
A
, V
B
, V
C
Uses V
S
• (PTRS/PTR) as
3V
0
a
a
The PTRS/PTR adjustment brings the broken-delta 3V
0
quantity to the same base voltage as
the relay impedance settings, which are based on the V
A
, V
B
, V
C
voltage base.
Wattmetric and incremental
conductance elements (ORDER
setting choice “P”).
Uses 3V
0
calculated
from V
A
, V
B
, V
C
Uses V
S
• (PTRS/PTR) as
3V
Synchronism check elements
Available
Not available
Three-phase power metering
(MW3P, MVAR3P, etc.)
No difference
Uses the sum of the single-phase power calculations
from V
A
, V
B
, V
C
, I
A
, I
B
, I
C
(primary values)
Quantity “3V0” in Metering,
Fast Meter, and Distributed
Network Protocol (DNP).
No difference
Uses 3V
0
calculated from V
A
, V
B
, V
C
(primary value)
Quantity “VS” in Metering,
Fast Meter, and DNP.
No difference
Uses V
S
as “VS” (primary value)
Summary of Contents for SEL-351A
Page 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...