12.4
SEL-351A Relay
Instruction Manual
Date Code 20080213
Standard Event Reports and SER
Standard 15/30-Cycle Event Reports
Standard Event
Report Summary
Each time the relay generates a standard event report, it also generates a
corresponding event summary (see
). Event summaries contain the
following information:
➤
Relay and terminal identifiers (settings RID and TID)
➤
Date and time when the event was triggered
➤
Event type
➤
Fault location
➤
Recloser shot count at the trigger time
➤
System frequency at the front of the event report
➤
Front-panel fault type targets at the time of trip
➤
Phase (IA, IB, IC), neutral-ground (IN), calculated residual-
ground (I
G
= 3I
0
), and negative-sequence (3I
2
) current
magnitudes in amps primary measured at the largest phase
current magnitude in the triggered event report
The Event Report Summary shows the magnitude of the maximum phase
current calculated by the cosine filter or bipolar peak detector. When the relay
uses the bipolar peak detector value, the relay displays
pk
as shown in the
Event Summary portion of the Example Standard 15-Cycle Event Report near
the end of this section (for more information on the cosine filter and bipolar
peak detector, see
CT Saturation Protection on page 1.4
The relay includes the event summary in the standard event report. The
identifiers, date, and time information is at the top of the standard event report,
and the other information follows at the end. See
The example event summary in
corresponds to the full-length
standard 15-cycle event report in
FEEDER 1 Date: 07/12/99 Time: 09:28:31.721
STATION A
Event: AG T Location: 2.36 Shot: 0 Frequency: 60.01
Targets: INST 50
Currents (A Pri), ABCNGQ: 2752 pk 209 209 1 2689 2689
Figure 12.1
Example Event Summary
The relay sends event summaries to all serial ports with setting AUTO = Y
each time an event triggers.
The latest event summaries are stored in nonvolatile memory and are accessed
by the
HIS
(Event Summaries/History) command.
Event Type
The
Event
field shows the event type. The possible event types and their
. Note the correspondence to the
preceding event report triggering conditions (see
).
NOTE:
is on multiple
pages.
Summary of Contents for SEL-351A
Page 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...