12.5
Date Code 20080213
Instruction Manual
SEL-351A Relay
Standard Event Reports and SER
Standard 15/30-Cycle Event Reports
The event type designations
AG
through
CAG
are only entered in
the
Event
field if the fault locator operates successfully. If the fault locator
does not operate successfully, just
TRIP
or
ER
is displayed.
Fault Location
The relay reports the fault location if the EFLOC setting = Y and the fault
locator operates successfully after an event report is generated. If the fault
locator does not operate successfully,
$$$$$$
is listed in the field. If EFLOC =
N, the field is blank. Fault location is based upon the line impedance settings
Z1MAG, Z1ANG, Z0MAG, and Z0ANG; source impedance settings
Z0SMAG and Z0SANG; and corresponding line length setting LL. See the
SET
and corresponding
Explanations on page 9.34) on page SET.1
for information on the line
parameter settings.
The fault locator algorithm uses the overcurrent elements 50P1–50P4, 50N1–
50N4, 50G1–50G4, 67Q1–67Q4, 51P, 51A, 51B, 51C, 51N, 51G, 51G2, and
51Q as fault detectors. If any of these elements are set to low pickup values for
use as load indicators, they may be asserted during non-fault conditions. In
this situation, even though these elements are not being used for tripping the
relay, they may still affect the operation of the fault locator, because the start
of the disturbance may be unclear. If load detectors are required in your
application, use the highest-numbered instantaneous overcurrent elements
50P5, 50P6, 50N5, 50N6, 50G5, 50G6, 50Q5, or 50Q6, because these are not
used by the fault locator algorithm.
Targets
The relay reports the targets at the rising edge of TRIP. The targets include:
INST
,
COMM
,
S0TF
,
50
,
51
, and
81
. If there is no rising edge of TRIP in the
report, the
Targets
field is blank. See
Front-Panel Target LEDS on page 5.10
.
Currents
The
Currents (A pri), ABCNGQ:
field shows the currents present in the event
report row containing the maximum phase current. The listed currents are:
Table 12.1
Event Types
Event Type
Description
AG, BG, CG
Single phase-to-ground faults. Appends T if TRIP asserted.
A, B, C
Single phase-to-ground faults (Petersen Coil and ungrounded/ high-
impedance grounded systems only). Appends T if TRIP asserted.
ABC
Three-phase faults. Appends T if TRIP asserted.
AB, BC, CA
Phase-to-phase faults. Appends T if TRIP asserted.
ABG, BCG, CAG
Phase-to-phase-to-ground faults. Appends T if TRIP asserted.
TRIP
Assertion of Relay Word bit TRIP
(fault locator could not operate successfully
to determine the phase involvement, so just TRIP is displayed).
ER
SEL
OGIC
control equation setting ER.
Phase involvement is indeterminate.
TRIG
Execution of
TRIGGER
command.
PULSE
Execution of
PULSE
command.
NOTES:
The fault locator will not
operate properly unless three-phase
voltages are connected.
The fault locator is most accurate
when the fault currents last longer
than two cycles.
The fault locator will not operate for
phase-to-ground faults on Petersen
Coil or ungrounded/high-impedance
grounded systems.
Summary of Contents for SEL-351A
Page 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...