4.31
Date Code 20050919
Instruction Manual
SEL-387-0, -5, -6 Relay
Control Logic
Relay Word Bits
PDEM1
Winding 1 phase demand current threshold exceeded
OCA
O/C element A-phase selection
3
50A13
Winding 1 A-phase instantaneous O/C Level 3 element picked up
50B13
Winding 1 B-phase instantaneous O/C Level 3 element picked up
50C13
Winding 1 C-phase instantaneous O/C Level 3 element picked up
50P13
50A13 + 50B13 + 50C13
50A14
Winding 1 A-phase instantaneous O/C Level 4 element picked up
50B14
Winding 1 B-phase instantaneous O/C Level 4 element picked up
50C14
Winding 1 C-phase instantaneous O/C Level 4 element picked up
50P14
50A14 + 50B14 + 50C14
4
50N11
Winding 1 residual definite-time O/C Level 1 element picked up
50N11T
Winding 1 residual definite-time O/C Level 1 element timed out
50N12
Winding 1 residual instantaneous O/C Level 2 element picked up
51N1
Winding 1 residual inverse-time O/C element picked up
51N1T
Winding 1 residual inverse-time O/C element timed out
51N1R
Winding 1 residual inverse-time O/C 51N1 element is reset
NDEM1
Winding 1 residual demand current threshold exceeded
OC1
Breaker 1
OPEN
command execution
5
50Q11
Winding 1 neg.-seq. definite-time O/C Level 1 element picked up
50Q11T
Winding 1 neg.-seq. definite-time O/C element timed out
50Q12
Winding 1 neg.-seq. instantaneous O/C Level 2 element picked up
51Q1
Winding 1 neg.-seq. inverse-time O/C element picked up
51Q1T
Winding 1 neg.-seq. inverse-time O/C element timed out
51Q1R
Winding 1 neg.-seq. inverse-time O/C 51Q1 element is reset
QDEM1
Winding 1 neg.-seq. demand current threshold exceeded
CC1
Breaker 1
CLOSE
command execution
6
50P21
Winding 2 phase definite-time O/C Level 1 element picked up
50P21T
Winding 2 phase definite-time O/C Level 1 element timed out
50P22
Winding 2 phase instantaneous O/C Level 2 element picked up
51P2
Winding 2 phase inverse-time O/C element picked up
51P2T
Winding 2 phase inverse-time O/C element timed out
51P2R
Winding 2 phase inverse-time O/C 51P2 element is reset
PDEM2
Winding 2 phase demand current threshold exceeded
OCB
O/C element B-phase selection
7
50A23
Winding 2 A-phase instantaneous O/C Level 3 element picked up
50B23
Winding 2 B-phase instantaneous O/C Level 3 element picked up
50C23
Winding 2 C-phase instantaneous O/C Level 3 element picked up
50P23
50A23 + 50B23 + 50C23
50A24
Winding 2 A-phase instantaneous O/C Level 4 element picked up
50B24
Winding 2 B-phase instantaneous O/C Level 4 element picked up
Table 4.10
Relay Word Bit Definitions
(Sheet 2 of 13)
Row
Bit
Definition
Summary of Contents for SEL-387-0
Page 10: ...This page intentionally left blank ...
Page 16: ...This page intentionally left blank ...
Page 56: ...This page intentionally left blank ...
Page 350: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 456: ...This page intentionally left blank ...
Page 494: ...This page intentionally left blank ...
Page 528: ...This page intentionally left blank ...