Serial Port Communications and Commands
SEL ASCII Protocol Details
If the relay reads the time code successfully, it updates the internal clock/
calendar time and date to the time-code reading. The relay then transmits a
message with relay settings RID and TID, and the date and time.
=>
IRI <Enter>
XFMR 1 Date: 02/01/96 Time: 01:45:40.762
STATION A
=>
If no IRIG-B signal is present or the code cannot be read successfully, the
relay sends the error message
IRIG-B DATA ERROR
.
MET (Metering Report)
Access Levels 1, B, 2
The
METER
command displays currents, demand currents, peak demand
currents, or differential data, depending on the command statement. There are
several choices for the
MET
command, listed briefly below. Refer to
Section 5: Metering and Monitoring
for a complete description of the
metering reports.
Use the
MET XXX
n
command, where
n
is a positive integer, to repeat the
MET XXX report
n
times. For example, to display a series of eight meter
readings, type
MET 8 <Enter>
.
If the Analog Input Label settings (IAW1, etc.) have been renamed, these will
appear in the report as set.
MET H (Harmonic Metering)
Access Levels 1, B, 2
The
METER H
command is different from the normal metering functions, in
that it uses 1 full cycle of unfiltered data, at 64 samples per cycle, to provide a
snapshot of total harmonic content of all 12 analog current inputs. It uses a
Fast Fourier transform technique to provide secondary current values for all
harmonics from 1 (fundamental) to 15.
This function is explained more fully in
Section 5: Metering and Monitoring
where a sample report also is shown. If the Analog Input Label settings
(IAW1, etc.) have been renamed, these will appear in the report as set.
NOTE:
Normally, it is not necessary
to synchronize using this command
because the relay automatically
synchronizes approximately once a
minute. The
IRIG
command is provided
to prevent delays during testing and
installation checkout.
Table 7.4
MET Command Choices
MET
Displays winding current metering data, in primary amperes
MET D
Displays winding demand ammeter data, in primary amperes
MET DIF
Displays differential metering data, in multiples of tap
MET H
Displays harmonic spectrum of currents (see
MET H
below)
MET P
Displays peak demand ammeter data, in primary amperes
MET RD
n
Resets demand ammeter for Winding
n
(
n
= 1, 2, 3, 4, A)
MET RP
n
Resets peak demand ammeter values
for Winding
n
(
n
= 1, 2, 3, 4, A)
MET SEC
Displays winding current metering data,
with magnitude and phase angle, in secondary amperes
MET T
Displays the temperature values of up to 12 RTDs per port
(maximum of
24 RTDs) (SEL-387-5 and SEL-387-6 relays only)
Summary of Contents for SEL-387-0
Page 10: ...This page intentionally left blank ...
Page 16: ...This page intentionally left blank ...
Page 56: ...This page intentionally left blank ...
Page 350: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 456: ...This page intentionally left blank ...
Page 494: ...This page intentionally left blank ...
Page 528: ...This page intentionally left blank ...