7.28
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20050919
Serial Port Communications and Commands
SEL ASCII Protocol Details
The two parameters are optional and perform the following functions:
➤
Setting
specifies the setting name with which to begin. The
default is the first setting.
➤
TERSE
eliminates the display of the global settings at the end
of the setting procedure. The command will function properly
if just
TE
is entered, instead of the full word.
The
SET G
procedure works just like the
SET
procedure.
lists the
editing keys that you can use with the
SET
command.
for all default settings and setting
worksheets.
SET P (Edit Port Settings)
Access Level 2
Configure the relay port settings using the
SET P
command. The port settings
include the communication and protocol settings. The entire syntax of the
SET P
command follows:
SET P
n
Setting TERSE <Enter>
The two parameters are optional and perform the following functions:
➤
n
specifies the serial port number (1, 2, 3, or 4). Default is the
port issuing the command.
➤
Setting
specifies the setting name with which to begin. The
default is the first setting.
➤
TERSE
eliminates the display of the port settings at the end of
the setting procedure.
The command will function properly if just
TE
is entered, instead of the full
word.
The
SET P
procedure works just like the
SET
procedure.
lists the
editing keys that you can use with the
SET
command.
The settings for each communication port are:
Table 7.6
Settings for Each Communication Port
PROTO
protocol can be SEL, LMD, DNP, RTDA, or RTDB.
PREFIX
If PROTO is LMD, prefix can be @, #, $, %, or &.
ADDR
If PROTO is LMD, ADDR can be any integer 1 through 99.
SETTLE
If PROTO is LMD, the settling time can be 0 to 30 seconds.
SPEED
baud can be set to 300, 1200, 2400, 4800, 9600, or 19200.
BITS
data can be 7 or 8 bits.
PARITY
can be O, E, or N (Odd, Even, None).
STOP
bits can be 1 or 2.
T_OUT
port inactivity time-out can be 0 through 30 minutes.
T_OUT = 0 setting means port will never time out.
Time-out returns port to Access Level 0.
AUTO
send auto messages to the port; Yes or No.
RTSCTS
enable hardware handshaking; Yes or No (only if PROTO = SEL).
FASTOP
enable Fast Operate function; Yes or No.
Summary of Contents for SEL-387-0
Page 10: ...This page intentionally left blank ...
Page 16: ...This page intentionally left blank ...
Page 56: ...This page intentionally left blank ...
Page 350: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 456: ...This page intentionally left blank ...
Page 494: ...This page intentionally left blank ...
Page 528: ...This page intentionally left blank ...