Compressed ASCII Commands
SEL-387-0, -5 Relay
The relay sends:
<STX>
"FID","yyyy"<CR>
"FID=SEL-387-XXXX-V0-ZXXXXXX-DXXXXXXXX","yyyy"<CR>
"MONTH_","DAY_","YEAR_","HOUR_","MIN_","SEC_","MSEC_","yyyy"<CR>
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,"yyyy"<CR>
"IAW1","IBW1","ICW1","IAW2","IBW2","ICW2","IAW3","IBW3","ICW3","IAW4",
"IBW4","ICW4","+5V_PS","+5V_REG","-5V_REG","+12V_PS","-12V_PS","+15V_PS",
"-15V_PS","TEMP","RAM","ROM","A/D","CR_RAM","EEPROM","IO_BRD","yyyy"<CR>
"xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx",
"xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xx
xx", "xxxx","xxxx","yyyy"<CR>
<ETX>
CTARGET Command
Display the SEL-387 Compressed ASCII target display by sending:
CTA
N
<Enter>
where
N
is one of the target numbers or element names accepted by the
TAR
command. If
N
is omitted, 0 is used.
The relay responds:
<STX>
"LLLL","LLLL","LLLL","LLLL","LLLL","LLLL","LLLL","LLLL","yyyy"<CR>
x,x,x,x,x,x,x,x,"yyyy"<CR>
<ETX>
where:
xxxx
= the data values corresponding to the first line labels.
yyyy
= the 4-byte ASCII representation of the hex checksum for
the line.
NOTE:
If the analog current input
names (
IAW1
, etc.) have been changed
via the Analog Input Labels global
settings, they will appear in the above
report as set.
where:
LLLL
= the labels for the given target.
x
= 0 or 1 corresponding to the first line labels.
yyyy
= the 4-byte ASCII representation of the hex checksum for
the line.
Summary of Contents for SEL-387-0
Page 10: ...This page intentionally left blank ...
Page 16: ...This page intentionally left blank ...
Page 56: ...This page intentionally left blank ...
Page 350: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 456: ...This page intentionally left blank ...
Page 494: ...This page intentionally left blank ...
Page 528: ...This page intentionally left blank ...