4.227
Date Code 20170814
Instruction Manual
SEL-700G Relay
Protection and Logic Functions
Front-Panel Settings (SET F Command)
Figure 4.152
Front-Panel Display—LV Breaker Closed
If you want the relay to display a blank state when IN101 deasserts instead of
removing the line altogether, use the curly brackets {} for the Clear String, as
follows:
When Input IN101 now deasserts, the relay still displays the line with the HV
breaker information, but the state is left blank, as shown in Figure 4.153.
Figure 4.153
Front-Panel Display—HV Breaker Open, LV Breaker Closed
Name Only
Table 4.85 shows an entry in the Name String only (leaving the Alias string,
Set String, and Clear String void), when you use the SET F command, as
follows:
Figure 4.154 shows the front-panel display for the entry in Table 4.85. Input
IN101 is deasserted in this display (
IN101=0
), but the display changes to
IN101=1
when Input IN101 asserts.
Figure 4.154
Front-Panel Display for a Binary Entry in the Name String Only
DP01 := RID, “{16}”
? IN101,"TRFR 1 HV BRKR:",CLOSED,{} <
Enter>
TRFR 1 LV BRKR:= CLOSED
TRFR 1 HV BRKR:=
TRFR 1 LV BRKR:= CLOSED
DP01 := RID, “{16}”
? IN101 <
Enter
>
Table 4.85
Binary Entry in the Name String Only
Name
Alias
Set String
Clear String
IN101
—
—
—
IN101=0
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...