5.17
Date Code 20170814
Instruction Manual
SEL-700G Relay
Metering and Monitoring
Breaker Monitor
Figure 5.17
Plotted Breaker Maintenance Points for a 25 kV Circuit Breaker
The following settings are made from the breaker maintenance information in
Table 5.10 and Figure 5.17:
COSP1n =
10000
COSP2n =
150
COSP3n =
12
KASP1n =
1.20
KASP2n =
8.00
KASP3n =
20.00
Figure 5.18 shows the resultant breaker maintenance curve.
10,000
1000
2
3
4
5
6
7
8
9
100
2
3
4
5
6
7
8
9
10
2
3
4
5
6
7
8
9
1
2
3
4
5
6 7 8 9
50
40
30
20
10
.5
Number of Close/Open Operations
kA Interrupted per Operation