Instruction Manual
SEL-700G Relay
Metering and Monitoring
Breaker Monitor
50 Percent to 100 Percent Breaker Wear
Refer to Figure 5.23. The current value changes from 12.0 kA to 1.5 kA.
1.5 kA is interrupted 3000 times (3000 close/open operations = 6000 – 3000),
pushing the breaker maintenance curve from the 50 percent wear level to the
100 percent wear level.
When the breaker maintenance curve reaches 100 percent for a particular
phase, the percentage wear remains at 100 percent (even if additional current
is interrupted), until reset by the BRE n R command (see View or Reset
Breaker Monitor Information on page 5.24). But the current and trip counts
continue to accumulate, until the BRE n R command resets these counts.
Additionally, logic outputs assert for alarm or other control applications—see
the following discussion.
Figure 5.23
Breaker Monitor Accumulates 100 Percent Wear
10,000
100%
1000
2
3
4
5
6
7
8
9
100
2
3
4
5
6
7
8
9
10
2
3
4
5
6
7
8
9
1
2
3
4
5
6 7 8 9
50
40
30
20
10
.5
Number of Close/Open Operations
kA Interrupted per Operation
50%
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...