Date Code 20170814
Instruction Manual
SEL-700G Relay
SEL-700G Settings Sheets
Instruction Manual
These settings sheets include the definition and input range for each setting in the relay. You can access the settings
from the relay front panel and the communications ports. See Section 4: Protection and Logic Functions in the
instruction manual for detailed descriptions of the settings.
➤
Some settings require an optional module. Refer to the SEL-700G Model Option Table, Table 1.1,
and the notes to the settings below for details on which settings are available in a specific model.
A
C
SEL
ERATOR
QuickSet SEL-5030 Software, which shows and hides settings depending on the
MOT part number selected, is the best way to view settings available in a specific model. Some of
the settings ranges may be more restrictive than shown because of settings interdependency checks
performed when new settings are saved
(
see Setting Entry Error Messages on page 6.6 of the
instruction manual)
➤
The settings are not case sensitive.
Group Settings (SET Command)
Identifier
Configuration
UNIT ID LINE 1 (16 Characters)
RID :=
UNIT ID LINE 2 (16 Characters)
TID :=
PHASE ROTATION (ABC, ACB)
PHROT :=
X-side
X CUR INPUT FROM (NEUT, TERM) (Shown if Slot
E
= 72/76, or Slot
E
= 73/77 and
Slot
Z
= 81/85/82/86, else hidden and auto-set to TERM)
X_CUR_IN :=
X PH CT RATIO (1–10000 [5 A I
XNOM
]; 1–50000 [1 A I
XNOM
])
(Hidden if Slot
Z
= 84/88)
CTRX :=
NOMINAL CURRENT (1.0–10.0 A [5 A I
XNOM
]; 0.2–2.0 A [1 A I
XNOM
])
(Hidden if Slot
Z
= 84/88/83/87)
INOM :=
X SIDE PT CONN (DELTA, WYE) (Hidden if Slot
Z
= 84/88/ 83/87)
DELTAY_X :=
X PH PT RATIO (1.00–10000.00) (Hidden if Slot
Z
= 84/88/83/87)
PTRX :=
X SIDE VNOM (0.02–1000.00 kV) (Hidden if Slot
Z
= 84/88/83/87)
VNOM_X :=
EXT ZERO SEQ VOLT (NONE, VS, VN) (Hidden if Slot
Z
= 84/88 or Slot
Z
= 83/87.
VS is hidden from the range if Slot
E
= 73/77 or Empty. VN is hidden from the range if
Slot
E
= 73/77, 71/75, or Empty.)
EXT3V0_X:=
Y-side
Y PH CT CONN (DELTA, WYE) (Hidden if Slot
Z
= 84/88/83/87 or if
Slot
E
= Empty/74/71/75)
CTCONY :=
Y PH CT RATIO (1–10000 [5 A I
YNOM
] 1–50000 [1 A I
YNOM
]) (Hidden if Slot
E
= Empty/74)
CTRY :=
Y SIDE PT CONN (DELTA, WYE) (Shown if Slot
E
= 71/75. If hidden, auto-set to
WYE)
DELTAY_Y :=
Y PH PT RATIO (1.00–10000.00) (Shown if Slot
E
= 71/75)
PTRY :=
Y SIDE VNOM (0.02–1000.00 kV) (Shown if Slot
E
= 71/75)
VNOM_Y :=
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...