7.47
Date Code 20170814
Instruction Manual
SEL-700G Relay
Communications
SEL ASCII Protocol and Commands
The elements are represented as Relay Word bits and are listed in rows of
eight, called Relay Word rows. The first four rows, representing the front-
panel operation and target LEDs, correspond to Table 7.56. All Relay Word
rows are described in Table J.1 and Table J.3.
Relay Word bits are used in SEL
OGIC
control equations. See Appendix J:
The TAR command does not remap the front-panel target LEDs, as is done in
some previous SEL relays.
TIME Command (View/Change Time)
The TIME command (see Table 7.57) returns information about the
SEL-700G internal clock. You can also set the clock if you specify hours and
minutes (seconds data are optional). Separate the hours, minutes, and seconds
with colons, semicolons, spaces, commas, or slashes.
Use the TIME hh:mm and TIME hh:mm:ss commands to set the internal
clock time. The value hh is for hours from 0–23; the value mm is for minutes
from 0–59; the value ss is for seconds from 0–59. If you enter a valid time, the
relay updates and saves the time in the nonvolatile clock, and displays the time
you just entered. If you enter an invalid time, the SEL-700G responds with
Invalid Time
.
TRIGGER Command (Trigger Event Report)
Use the TRI command (see Table 7.58) to trigger the SEL-700G to record
data for the high-resolution oscillography and event reports.
When you issue the TRI command, the SEL-700G responds with
Triggered
.
If the event did not trigger within one second, the relay responds with
Did not
trigger
. See Section 9: Analyzing Events for further details on event reports.
Table 7.56
Front-Panel LEDs and the TAR 0 Command
LEDs
7
6
5
4
3
2
1
0
TAR 0
ENABLED
TRIP_LED
TLED_01
TLED_02
TLED_03
TLED_04
TLED_05
TLED_06
Table 7.57
TIME Command (View/Change Time)
Command
Description
Access Level
TIME
Display the present internal clock time.
1
TIME hh:mm
Set the internal clock to hh:mm.
1
TIME hh:mm:ss
Set the internal clock to hh:mm:ss.
1
Table 7.58
TRIGGER Command (Trigger Event Report)
Command
Description
Access Level
TRI
Trigger event report data capture.
1
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...