A.3
Date Code 20170814
Instruction Manual
SEL-700G Relay
Firmware and Manual Versions
Firmware
➤
Changed the storage of latch and local bits from volatile to
nonvolatile memory.
➤
Modified the firmware to make the MATHERR Relay
Word bit visible.
➤
Added Y-MODEM over Telnet to support file transfer.
➤
Revised the firmware to support front-panel HMI part
replacement; the function of the HMI has not changed.
➤
Resolved an issue in R100–R106 firmware versions where
the relay reported RTD failure when both the SEL-2600
(RTD Module) and the SEL-2664 (Field Ground Module)
were connected and simultaneously communicating with
the relay.
➤
Modified the firmware to report the field resistance value as
FFFFh instead of 0 in DNP, Modbus, and IEC 61850 when
E64F := N or 64FFLT = 1. Analog quantity FLDRES will
report a value of 20 Mohm instead of 0 when E64F := N or
64FFLT = 1.
➤
Modified the firmware to show *FAIL* instead of zero in
the MET response for the Field Resistance measurement
when E64F = Y and the data are invalid.
➤
Resolved an issue with setting ALTCOOL at a value other
than zero when GTC2 = OFF.
➤
Resolved an issue with the thermal element (49T) when
GTC1 is set to a value greater than 326 minutes.
➤
Resolved as issue that can cause small jumps in the angle
calculations for analog quantities.
➤
Addressed an issue with validating the IPADDR,
SUBNETM, DEFRTR, and other IP address and port num-
ber settings of enabled protocols.
➤
Revised the firmware to allow anonymous TCP connection
from DNP masters when DNPIPx is set to 0.0.0.0.
➤
Resolved an issue with settings change (STSET) being
reported as OFFLINE via DNP.
➤
Resolved an issue with the DNP Binary Outputs so that
they are no longer reported as OFFLINE when the Binary
Output is also present in the Binary Input map and the
Sequential Events Recorder (SER).
➤
Modified the default data set and report names in the 61850
CID file. Added additional Logical Nodes for Local Bits
and M
IRRORED
B
ITS
status.
SEL-700G-R106-V0-Z003002-D20130405
➤
Corrected an issue with MET PM, which used UTC time to
trigger instead of local time.
➤
Improved the synchrophasor algorithm to yield better pha-
sor-based frequency measurements.
➤
Corrected an issue where the front panel showed a blank
page after target resetting the TRIP.
➤
Corrected an issue with the data type “Units_0” in the
IEC 61850 ICD file by changing the unit data type name to
SI Unit.
➤
Added a feature in Modbus to always show the latest event
data unless another event is selected.
➤
Improved frequency tracking switching (from X side to
Y side) when VAX was removed/reduced.
➤
RTS is forced high and CTS is ignored when the PREDLY
setting is OFF to power certain fiber-optic transceivers.
20130405
Table A.1
Firmware Revision History
(Sheet 3 of 5)
Firmware Identification (FID) Number
Summary of Revisions
Manual Date Code
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...