F.24
SEL-700G Relay
Instruction Manual
Date Code 20170814
IEC 61850 Communications
Logical Nodes
P51VPVOC2
Op.general
51VT
Voltage-Restrained Phase Time-Overcurrent Element 51VT timed out
P51VPVOC2
Str.general
51V
Voltage-restrained phase time-overcurrent element pickup
P51VPVOC2
Str.dirGeneral
unknown
Direction unknown due to settings
PX1PIOC1
Op.general
50PX1T
X-Side, Level 1 phase instantaneous overcurrent element trip
PX1PIOC1
Str.general
50PX1P
X-Side, Level 1 phase instantaneous overcurrent element pickup
PX1PIOC1
Str.dirGeneral
unknown
Direction undefined
PX1PTOV1
Op.general
59PX1T
X-Side, Level 1 phase overvoltage element trip
PX1PTOV1
Str.general
59PX1
X-Side, Level 1 phase overvoltage element pickup
PX1PTOV1
Str.dirGeneral
unknown
Direction undefined
PX1PTUV1
Op.general
27PX1T
X-Side, Level 1 phase undervoltage element trip
PX1PTUV1
Str.general
27PX1
X-Side, Level 1 phase undervoltage element pickup
PX1PTUV1
Str.dirGeneral
unknown
Direction undefined
PX2PIOC2
Op.general
50PX2T
X-Side, Level 2 phase instantaneous overcurrent element trip
PX2PIOC2
Str.general
50PX2P
X-Side, Level 2 phase instantaneous overcurrent element pickup
PX2PIOC2
Str.dirGeneral
unknown
Direction undefined
PX2PTOV2
Op.general
59PX2T
X-Side, Level 2 phase overvoltage element trip
PX2PTOV2
Str.general
59PX2
X-Side, Level 2 phase overvoltage element pickup
PX2PTOV2
Str.dirGeneral
unknown
Direction undefined
PX2PTUV2
Op.general
27PX2T
X-Side, Level 2 phase undervoltage element trip
PX2PTUV2
Str.general
27PX2
X-Side, Level 2 phase undervoltage element pickup
PX2PTUV2
Str.dirGeneral
unknown
Direction undefined
PXAPIOC3
Op.general
50PX3AT
X-Side, Level 3 Phase A instantaneous overcurrent element trip
PXAPIOC3
Str.general
50PX3AP
X-Side, Level 3 Phase A instantaneous overcurrent element pickup
PXAPIOC3
Str.dirGeneral
unknown
Direction undefined
PXBPIOC4
Op.general
50PX3BT
X-Side, Level 3 Phase B instantaneous overcurrent element trip
PXBPIOC4
Str.general
50PX3BP
X-Side, Level 3 Phase B instantaneous overcurrent element pickup
PXBPIOC4
Str.dirGeneral
unknown
Direction undefined
PXCPIOC5
Op.general
50PX3CT
X-Side, Level 3 Phase C instantaneous overcurrent element trip
PXCPIOC5
Str.general
50PX3CP
X-Side, Level 3 Phase C instantaneous overcurrent element pickup
PXCPIOC5
Str.dirGeneral
unknown
Direction undefined
PXPTOC9
Op.general
51PXT
X-side phase time overcurrent element trip
PXPTOC9
Str.general
51PXP
X-side phase time overcurrent element pickup
PXPTOC9
Str.dirGeneral
unknown
Direction unknown due to settings
PY1PIOC6
Op.general
50PY1T
Y-Side, Level 1 phase instantaneous overcurrent element trip
PY1PIOC6
Str.general
50PY1P
Y-Side, Level 1 phase instantaneous overcurrent element pickup
PY1PIOC6
Str.dirGeneral
unknown
Direction undefined
PY1PTOC5
Op.general
67PY1T
Y-Side, Level 1 phase directional overcurrent trip
PY1PTOC5
Str.general
67PY1P
Y-Side, Level 1 phase directional overcurrent pickup
PY1PTOC5
Str.dirGeneral
unknown
Direction unknown due to settings
Table F.16
Logical Device: PRO (Protection)
(Sheet 7 of 11)
Logical Node
Attribute
Data Source
Comment
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...