J.18
SEL-700G Relay
Instruction Manual
Date Code 20170814
Relay Word Bits
Definitions
BFIX
52X Breaker Failure Initiation asserted
32
BFIY
52Y Breaker Failure Initiation asserted
32
BFTX
52X Breaker Failure trip
23
BKRCF
Generator breaker close failed
36
BND1A
Abnormal Frequency Band 1 alarm (measured frequency between UBND1 and LBND1
settings
60
BND1T
Abnormal Frequency Band 1 trip (accumulated off-frequency operating time in band 1
exceeds TBND1 setting)
32
BND2A
Abnormal Frequency Band 2 alarm (measured frequency between LBND1 and LBND2
settings)
60
BND2T
Abnormal Frequency Band 2 trip (accumulated off-frequency operating time in band 2
exceeds TBND2 setting)
32
BND3A
Abnormal Frequency Band 3 alarm (measured frequency between LBND2 and LBND3
settings)
60
BND3T
Abnormal Frequency Band 3 trip (accumulated off-frequency operating time in band 3
exceeds TBND3 setting)
32
BND4A
Abnormal Frequency Band 4 alarm (measured frequency between LBND3 and LBND4
settings)
60
BND4T
Abnormal Frequency Band 4 trip (accumulated off-frequency operating time in band 4
exceeds TBND4 setting)
32
BND5A
Abnormal Frequency Band 5 alarm (measured frequency between LBND4 and LBND5
settings)
60
BND5T
Abnormal Frequency Band 5 trip (accumulated off-frequency operating time in band 5
exceeds TBND5 setting)
32
BND6A
Abnormal Frequency Band 6 alarm (measured frequency between LBND5 and LBND6
settings)
60
BND6T
Abnormal Frequency Band 6 trip (accumulated off-frequency operating time in band 6
exceeds TBND6 setting)
32
BNDA
BNDA = BND1A OR BND2A OR BND3A OR BND4A OR BND5A OR BND6A
60
BNDT
BNDT = BND1T OR BND2T OR BND3T OR BND4T OR BND5T OR BND6T
22
BRGALRM
Bearing Temperature Alarm. BRGALRM asserts when any healthy bearing RTD
temperature exceeds its alarm setpoint, or biased alarm setpoint.
44
BRGTRIP
Bearing Temperature trip and Alarm. BRGTRIP asserts when one or two (when
EBRGV = Y) healthy winding RTD temperatures exceed their trip or biased trip (when
RTDBIAS = Y) setpoints.
44
CBADA
Channel A, channel unavailability over threshold
102
CBADB
Channel B, channel unavailability over threshold
102
CCX
Close command—asserts when serial port command CCX (CLOSE Breaker X) or Front
Panel or Modbus/ DeviceNet Close command is issued to Close Breaker X
40
CCY
Close command—asserts when serial port command CCY (CLOSE Breaker Y) or Front
Panel or Modbus/ DeviceNet Close command is issued to Close Breaker Y
40
CFA
Generator breaker close failure angle condition
36
CFGFLT
Asserts on failed settings interdependency check during Modbus setting change
54
CFX
Breaker X close condition failure on
40
CFY
Breaker Y close condition failure on
40
Table J.3
Relay Word Bit Definitions for the SEL-700G
(Sheet 12 of 22)
Bit
Definition
Row
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...