4.139
Date Code 20170814
Instruction Manual
SEL-700G Relay
Protection and Logic Functions
Group Settings (SET Command)
Set EPWR to N (None) or as many as four power elements, as necessary for
your application. Set the element pickup, 3PH PWR ELEM PU to the values
you want. Figure 4.96 shows the power element logic diagram, and
Figure 4.97 shows the operation in the real/reactive power plane.
Figure 4.96
Three-Phase Power Elements Logic
PWR ELEM DELAY
0.00–240.00 s
PWRm3D := 0.00
3PH PWR ELEM PU
OFF, 1.0–6500.0 VA
(secondary VA)
b
3PWRm4P := OFF
PWR ELEM TYPE
+WATTS, –WATTS,
+VARS, –VARS
PWRm4T := +VARS
PWR ELEM DELAY
0.00–240.00 s
PWRm4D := 0.00
a
m = X or Y.
b
The ranges and default settings shown are for 5 A input. Divide by 5 for 1 A input.
Table 4.38
Power Element Settings
(Sheet 2 of 2)
Setting Prompt
Setting Range
Setting Name :=
Factory Default
a
PWRXnD
0
3PWRXnP
|VABX|
20 V
3PWRXnT
Relay
Word
Bits
Switch A
Position
+WATTS
–WATTS
+VARS
–VARS
Setting
PWRXnT
1
1
2
2
Switch B
Position
1
2
1
2
2 Cycle
Average
•(–1)
Switch A
Switch B
1
1
2
2
3PWRXnP
|VBCX|
Setting
P
Q
Where n = 1, 2, 3, or 4.
Only X side logic shown, Y side is similar.
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...