4.218
SEL-700G Relay
Instruction Manual
Date Code 20170814
Protection and Logic Functions
Global Settings (SET G Command)
Figure 4.147
Timing Diagram for Debounce Timer Operation When Operating
in AC Mode
Deassertion follows the same logic. On the falling edge of IN101R, the
dropout timer starts timing. If IN101R remains deasserted for a period longer
than the dropout timer setting, then Relay Word bit IN101 deasserts to a
logical 0.
Table 4.70 shows the settings prompt, the setting range, and the factory-
default settings for a card in Slot
C
. See the SEL-700G Settings Sheets for a
complete list of the input debounce settings.
Data Reset
The RSTTRGT setting resets the trip output and front-panel
TRIP
LED,
provided that there is no trip condition present. See Figure 4.123 for more
details. The RSTENRGY and RSTMXMN settings reset the Energy and Max/
Min Metering values, respectively. You should assign a contact input (for
example, RSTTRGT := IN401) to each of these settings if you want remote
reset. The RSTDEM and RSTPKDEM settings reset demand and peak-
demand. See Figure 4.121 for the demand current logic diagram.
Table 4.70
Slot C Input Debounce Settings
Setting Prompt
Setting Range
Setting Name :=
Factory Default
IN301 Debounce
AC, 0–65000 ms
IN301D := 10
IN302 Debounce
AC, 0–65000 ms
IN302D := 10
IN303 Debounce
AC, 0–65000 ms
IN303D := 10
IN304 Debounce
AC, 0–65000 ms
IN304D := 10
IN305 Debounce
AC, 0–65000 ms
IN305D := 10
IN306 Debounce
AC, 0–65000 ms
IN306D := 10
IN307 Debounce
AC, 0–65000 ms
IN307D := 10
IN308 Debounce
AC, 0–65000 ms
IN308D := 10
IN101R
2 ms
IN101R Deasserted;
DDOT Counts
IN101R Deasserted;
DDOT Counts
Dropout Time
(16 ms)
Debounce Dropout
Timer Expires;
Relay Word Bit
IN101 Deasserts
Debounce Pickup
Timer Expires;
Relay Word Bit
IN101 Asserts
IN101R Asserted;
DPUT Counts
IN101R Asserted;
DPUT counts
Relay Word
Bit IN101
1
2
1
1 1
1 1
2
2 2
2 2
DPUT = Debounce Pickup Timer
DDOT = Debounce Dropout Timer
1 = Rising Edge: DPUT Counts
2 = Falling Edge: DDOT Counts
Table 4.71
Data Reset Settings
(Sheet 1 of 2)
Setting Prompt
Setting Range
Setting Name :=
Factory Default
RESET TARGETS
SEL
OGIC
RSTTRGT := 0
RESET ENERGY
SEL
OGIC
RSTENRGY := 0
RESET MAX/MIN
SEL
OGIC
RSTMXMN := 0
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...