4.220
SEL-700G Relay
Instruction Manual
Date Code 20170814
Protection and Logic Functions
Port Settings (SET P Command)
PORT F
PORT 1
Table 4.74
Front-Panel Serial Port Settings
Setting Prompt
Setting Range
Setting Name :=
Factory Default
PROTOCOL
SEL, MOD,
EVMSG, PMU
PROTO := SEL
SPEED
300–38400 bps
SPEED := 9600
DATA BITS
7, 8 bits
BITS := 8
PARITY
O, E, N
PARITY := N
STOP BITS
1, 2 bits
STOP := 1
PORT TIME-OUT
0–30 min
T_OUT := 5
SEND AUTOMESSAGE
Y, N
AUTO := N
HDWR HANDSHAKING
Y, N
RTSCTS := N
MODBUS SLAVE ID
1–247
SLAVEID := 1
Table 4.75
Ethernet Port Settings
Setting Prompt
Setting Range
Setting Name :=
Factory Default
IP ADDRESS
zzz.yyy.xxx.www
IPADDR := 192.168.1.2
SUBNET MASK
15 characters
SUBNETM :=
255.255.255.0
DEFAULT ROUTER
15 characters
DEFRTR := 192.168.1.1
Enable TCP Keep-Alive
(Y, N)
ETCPKA := Y
TCP Keep-Alive Idle Range
1–20 sec
KAIDLE := 10
TCP Keep-Alive Interval Range
1–20 sec
KAINTV := 1
TCP Keep-Alive Count Range
1–20
KACNT := 6
SEND AUTOMESSAGES
Y, N
AUTO := N
FAST OP MESSAGES
Y, N
FASTOP := N
OPERATING MODE
FIXED, FAILOVER,
SWITCHED
NETMODE := FAILOVER
FAILOVER TIMEOUT
OFF, 0.10–65.00 sec
FTIME := 1.00
PRIMARY NETPORT
A, B
NETPORT := A
NETWRK PORTA SPD
AUTO, 10, 100 Mbps
NETASPD := AUTO
NETWRK PORTB SPD
AUTO, 10, 100 Mbps
NETBSPD := AUTO
TELNET PORT
23, 1025–65534
TPORT := 23
TELNET TIME OUT
1–30 min
TIDLE := 15
FTP USER NAME
20 characters
FTPUSER := FTPUSER
Enable IEC 61850 Protocol
(Y, N)
E61850 := N
Enable IEC 61850 GSE
(Y, N)
EGSE := N
Enable Modbus Sessions
0–2
EMOD := 0
Modbus TCP Port 1
(1–65534)
MODNUM1 := 502
Modbus TCP Port 2
(1–65534)
MODNUM2 := 502
Enable PMU Processing
a
a
See Appendix H: Synchrophasors for a complete list of Synchrophasor settings and their
descriptions.
0–2
EPMIP := 0
Enable DNP Session
b
b
See Table D.7 for a complete list of the DNP3 session settings.
0–3
EDNP := 0
IMPORTANT:
On relay initial power
up or Port 1 setting changes or Logic
setting changes, you may have to wait
as long as two minutes before an
additional setting change can occur.
Note that the relay is functional with
protection enabled, as soon as the
ENABLED LED
comes ON (about 5—10
seconds from power up).
NOTE:
TCP Keep-Alive is enabled
with default range settings for PMU
TCP sessions even when
ETCPKA := N.
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...