4.221
Date Code 20170814
Instruction Manual
SEL-700G Relay
Protection and Logic Functions
Port Settings (SET P Command)
Port Number Settings Must be Unique
When making the SEL-700G Port 1 settings, port number settings cannot be
used for more than one protocol. The relay checks all of the settings shown in
Table 4.76 before saving changes. If a port number is used more than once, or
if it matches any of the fixed port numbers (20, 21, 23, 102, 502), the relay
displays an error message and returns to the first setting that is in error or
contains a duplicate value.
PORT 2
PORT 3
Table 4.76
Port Number Settings That Must be Unique
Setting
Name
Setting Required When
TPORT
Telnet Port
Always
MODNUM1
a
a
MODNUM1 and MODNUM2 can have the same port number. The relay displays an error message if this number matches with the port
numbers of the other protocols.
Modbus TCP Port 1
EMOD > 0
MODNUM2
Modbus TCP Port 2
EMOD > 1
PMOTCP1
PMU Output 1 TCP/IP (Local) Port Number
PMOTS1 = TCP, UDP_T, or UDP_U
PMOTCP2
PMU Output 2 TCP/IP (Local) Port Number
PMOTS2 = TCP, UDP_T, or UDP_U
DNPNUM
DNPTCP and UDP Port
EDNP > 0
SNTPPORT
SNTPIP (Local) Port Number
ESNTP
OFF
Table 4.77
Fiber-Optic Serial Port Settings
Setting Prompt
Setting Range
Setting Name :=
Factory Default
PROTOCOL
SEL, DNP, MOD, EVMSG, PMU, MBA,
MBB, MB8A, MB8B, MBTA, MBTB
PROTO := SEL
SPEED
300–38400 bps
SPEED := 9600
DATA BITS
7, 8 bits
BITS := 8
PARITY
O, E, N
PARITY := N
STOP BITS
1, 2 bits
STOP := 1
PORT TIME-OUT
0–30 min
T_OUT := 5
SEND AUTOMESSAGE
Y, N
AUTO := N
FAST OP MESSAGES
Y, N
FASTOP := N
MODBUS SLAVE ID
1–247
SLAVEID := 1
NOTE:
For additional settings when
PROTO := MBxx, see Table I.5 as well
as M
is not MBxx on any of the
communications ports) on
page SET.36
. For additional settings
when PROTO := DNP, see Table D.7 for
a complete list of the DNP3 session
settings.
Table 4.78
Rear-Panel Serial Port (EIA-232) Settings
(Sheet 1 of 2)
Setting Prompt
Setting Range
Setting Name :=
Factory Default
PROTOCOL
SEL, DNP, MOD, EVMSG, PMU, MBA,
MBB, MB8A, MB8B, MBTA, MBTB
PROTO := SEL
SPEED
300–38400 bps
SPEED := 9600
DATA BITS
7, 8 bits
BITS := 8
PARITY
O, E, N
PARITY := N
STOP BITS
1, 2 bits
STOP := 1
PORT TIMEOUT
0–30 min
T_OUT := 5
SEND AUTOMESSAGE
Y, N
AUTO := N
HDWR HANDSHAKING
Y, N
RTSCTS := N
NOTE:
For additional settings when
PROTO := MBxx, see Table I.5 as well
as M
is not MBxx on any of the
communications ports) on
page SET.36
. For additional settings
when PROTO := DNP, see Table D.7 for
a complete list of the DNP3 session
settings.
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...