5.16
SEL-700G Relay
Instruction Manual
Date Code 20170814
Metering and Monitoring
Breaker Monitor
These three points are entered with the settings in Table 5.11.
Table 5.11
Breaker Monitor Settings
a
a
n = X or Y.
Setting Prompt
Setting Range
Setting Name :=
Breakern Monitor
(Y, N)
EBMONn := Y
nCL/OPN OPS SETPT 1
(0–65000)
COSP1n := 10000
b
b
COSP1n must be set greater than COSP2n.
nCL/OPN OPS SETPT 2
(0–65000)
COSP2n := 150
c d
c
COSP2n must be set greater than or equal to COSP3n.
d
If COSP2n is set the same as COSP3n, then KASP2 must be set the same as KASP3n.
nCL/OPN OPS SETPT 3
(0–65000)
COSP2n := 12
nkA PRI INTERRPTD 1
(0.10–999.00 kA)
KASP1n := 1.20
e
e
KASP1n must be set less than KASP2n.
nkA PRI INTERRPTD 2
(0.10–999.00 kA)
KASP2n := 8.00
nkA PRI INTERRPTD 3
(0.10–999.00 kA)
KASP3n := 20.00
f
f
KASP3n must be set at least five times (but no more than 100 times) the KASP1n setting
value.
BRKRn MON CONTROL
SEL
OGIC
BKMONn := TRIP
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...