6.4
SEL-700G Relay
Instruction Manual
Date Code 20170814
Settings
View/Change Settings Over Communications Port
View/Change Settings Over Communications Port
Refer to Section 7: Communications for information on how to set up and
access the relay serial or Ethernet port with a personal computer and how to
use ASCII commands to communicate with the relay.
View Settings
Use the SHOW command to view relay settings. The SHOW command is
available from Access Level 1 and Access Level 2. Table 6.2 lists the SHOW
command options.
Append a setting name to each of the commands to specify the first setting to
display (for example, SHO 50PX1P displays the relay settings starting with
setting 50PX1P). The default is the first setting. The SHOW command
displays only the enabled settings.
Enter Settings
The SET command (available from Access Level 2) allows you to view or
change settings. Table 6.3 lists the SET command options.
Append a setting name to each of the commands to specify the first setting to
display (for example, SET 50PX1P displays the relay settings starting with
setting 50PX1P). The default is the first setting.
Table 6.2
SHOW Command Options
Command
Description
SHOW n
Show relay group settings: n specifies the settings group (1, 2, or 3); n
defaults to active settings group if not listed.
SHO L n
Show logic settings: n specifies the settings group (1, 2, or 3); n defaults to
active settings group if not listed.
SHO G
Show global configuration settings.
SHO P n
Show serial port settings for port n (n = F, 1, 2, 3, or 4).
SHO F
Show front-panel display and LED settings.
SHO R
Show Sequential Event Report (SER) and Event Report settings.
SHO M
Show Modbus settings.
SHO D
Show DNP3 map settings.
Table 6.3
SET Command Options
Command
Settings Type
Description
SET n
Relay
Protection elements, timers, etc., for settings group n
(1, 2, or 3)
SET L n
Logic
SEL
OGIC
control equations for settings group n
(1, 2, or 3)
SET G
Relay
Global configuration settings including Event Messen-
ger, optoisolated input debounce timers, etc.
SET P n
Port
Serial port settings for serial port n (1, 2, 3, 4, or F)
SET F
Front Panel
Front-panel display and LED settings
SET R
Reports
SER and Event Report settings
SET M
Modbus
Modbus user map
SET D
DNP
DNP3 map settings
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...