7.38
SEL-700G Relay
Instruction Manual
Date Code 20170814
Communications
SEL ASCII Protocol and Commands
Examples of valid, distinct, and strong passwords are as follows:
➤
#0t3579!ijd7
➤
(Ih2dcs)36dn
➤
$
A24.68&,mvj
➤
*4u-Iwg+?lf-
PING Command
When you are setting up or testing substation networks, it is helpful to
determine if the network is connected properly and if the other devices are
powered up and configured properly. The PING command (Access Level 2)
allows a user of the relay to determine if a host is reachable across an IP
network and/or if the Ethernet port (Port 1) is functioning or configured
correctly. A typical PING command response is shown in Figure 7.25.
The command structure is:
PING x.x.x.x t
where:
x.x.x.x is the Host IP address and
“t” is the PING interval in seconds, with a 2 to 255 second range.
The default PING interval is one second when ‘t’ is not specified. The relay
sends ping messages to the remote node until you stop the PING test by
pressing the Q key.
PULSE Command
Use the PULSE command (see Table 7.39) to pulse any of the relay control
outputs for a specified time. This function aids you in relay testing and
commissioning. When a PUL command is issued, the selected contact will
close or open depending on the output contact type (a or b). The PUL
command energizes the coil and does not have any effect if the coil is already
energized. The control outputs are OUTnnn, where nnn represents the output
location by card slot position (first digit) and output number (second and third
digit). For example, OUTPUT 301 refers to output 01 in slot
3
(Slot
C
).
==>>
PING 10.201.7.52 <Enter>
Press the Q key to end the ping test.
Pinging 10.201.7.52 every 1 second(s):
Reply from 10.201.7.52
Reply from 10.201.7.52
Reply from 10.201.7.52
Reply from 10.201.7.52
Reply from 10.201.7.52
Reply from 10.201.7.52
Ping test stopped.
Ping Statistics for 10.201.7.52
Packets: Sent = 7, Received = 6, Lost = 1
Duplicated = 0
==>>
Figure 7.25
PING Command Response
NOTE:
The
PULSE
command is
available when the breaker control
jumper on the main board is in the
ENABLED position.
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...