7.45
Date Code 20170814
Instruction Manual
SEL-700G Relay
Communications
SEL ASCII Protocol and Commands
Refer to Figure 1.3 and Figure 1.4 for STATUS command response outputs.
Figure 7.27 shows the typical relay output for the STATUS S command,
showing available SEL
OGIC
control equation capability.
FPGA
FPGA programming unsuccessful, or FPGA failed
OK/FAIL
GPSB
General Purpose Serial Bus
OK/FAIL
HMI
Front-Panel FGPA programming unsuccessful, or Front-Panel
FPGA failed
OK/WARN
RAM
Volatile memory integrity
OK/FAIL
ROM
Firmware integrity
OK/FAIL
CR_RAM
Integrity of settings in RAM and code that runs in RAM
OK/FAIL
Non_Vol
Integrity of data stored in nonvolatile memory
OK/FAIL
Clock
Clock functionality
OK/WARN
RTD
Integrity of RTD module/communications
OK/FAIL
CID_FILE
Configured IED description file
OK/FAIL
x.x V
Power supply status
Voltage/FAIL
BATT
Clock battery voltage
Voltage/WARN
CARD_C
Integrity of Card C
OK/FAIL
CARD_D
Integrity of Card D
OK/FAIL
CARD_E
Integrity of Card E
OK/FAIL
CARD_Z
Integrity of Card Z
OK/FAIL
DN_MAC_ID
Specific DeviceNet card identification
Text Data
ASA
Manufacturers identifier for DeviceNet
Text Data
DN_Rate
DeviceNet card network communications data rate ___kbps
Text Data
DN_Status
DeviceNet connection and fault status 000b bbbb
Text Data
Current Offset (IAn, IBn, ICn, IN)
DC offset in hardware circuits of current channels, n = X or Y
Voltage/WARN
Voltage Offset (VAn, VBn, VCn, VS, VN)
DC offset in hardware circuits of voltage channels, n = X or Y
Voltage/WARN
Field Ground Module—COMM
SEL-2664 to SEL-700G communication status
OK/FAIL
Field Ground Module—MODULE
SEL-2664 FGM self-test status
OK/FAIL/NA
Table 7.51
STATUS Command Report and Definitions
(Sheet 2 of 2)
STATUS Report Designator
Definition
Message Format
=>>
STA S <Enter>
SEL-700GT Date: 03/02/2010 Time: 10:29:01.041
INTERTIE RELAY Time Source: Internal
Part Number = 0700GT1B1X0X7585063X
SEL
OGIC
Equation Available Capacity
Global (%) 74
FP (%) 50
Report (%) 95
GROUP 1 GROUP 2 GROUP 3
Execution (%) 79 79 79
Group (%) 83 83 83
Logic (%) 87 87 87
=>>
Figure 7.27
Typical Relay Output for STATUS S Command
NOTE:
The STA S report gives the
available SEL
OGIC
capacity of the
relay. For example, Execution 90%
mean 90% of execution capacity is
still available.
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...