D.3
Date Code 20170814
Instruction Manual
SEL-700G Relay
DNP3 Communications
Introduction to DNP3
Qualifier Codes and Ranges
DNP3 masters use qualifier codes and ranges to make requests for specific
objects by index. Qualifier codes specify the style of range, and the range
specifies the indices of the objects of interest. DNP3 masters use qualifier
codes to compose the shortest, most concise message possible when
requesting points from a DNP3 outstation.
For example, the qualifier code 01 specifies that the request for points includes
a start address and a stop address. Each of these two addresses uses two bytes.
An example request using qualifier code 01 might have the four hexadecimal
byte range field, 00h 04h 00h 10h, which specifies points in the range 4 to 16.
Access Methods
DNP3 has many features that help obtain maximum possible message
efficiency. DNP3 masters send requests with the least number of bytes using
special objects, variations, and qualifiers that reduce the message size. Other
features eliminate the continual exchange of static (unchanging) data values.
These features optimize use of bandwidth and maximize performance over a
connection of any speed.
DNP3 event data collection eliminates the need to use bandwidth to transmit
values that have not changed. Event data are time-stamped records that show
when observed measurements changed. For binary points, the remote device
(DNP3 outstation) logs changes from logical 1 to logical 0 and from logical 0
to logical 1. For analog points, the outstation device logs changes that exceed
a dead band. DNP3 outstation devices collect event data in a buffer that either
the master can request or the device can send to the master without a request
message. Data sent from the outstation to the master without a polling request
are called unsolicited data.
DNP3 data fit into one of four event classes: 0, 1, 2, or 3. Class 0 is reserved
for reading the present value data (static data). Classes 1, 2, and 3 are event
data classes. The meaning of Classes 1 to 3 is arbitrary and defined by the
application at hand. With outstations that contain great amounts of data or in
large systems, the three event classes provide a framework for prioritizing
different types of data. For example, you can poll once a minute for Class 1
data, once an hour for Class 2 data, and once a day for Class 3 data.
DNP3 also supports static polling: simple polling of the present value of data
points within the outstation. By combining event data, unsolicited polling, and
static polling, you can operate your system in one of the four access methods
shown in Table D.3.
The access methods listed in Table D.3 are listed in order of increasing
communication efficiency. With various trade-offs, each method is less
demanding of communication bandwidth than the previous one. For example,
unsolicited report-by-exception consumes less communication bandwidth
Table D.2
Selected DNP3 Function Codes
Function
Code
Function
Description
1
Read
Request data from the outstation
2
Write
Send data to the outstation
3
Select
First part of a Select-Before-Operate operation
4
Operate
Second part of a Select-Before-Operate operation
5
Direct operate
One-step operation with reply
6
Direct operate, no reply
One-step operation with no reply
Summary of Contents for SEL-700G Series
Page 14: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 32: ...This page intentionally left blank ...
Page 52: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 510: ...This page intentionally left blank ...
Page 560: ...This page intentionally left blank ...
Page 578: ...This page intentionally left blank ...
Page 588: ...This page intentionally left blank ...
Page 604: ...This page intentionally left blank ...
Page 634: ...This page intentionally left blank ...
Page 738: ...This page intentionally left blank ...
Page 802: ...This page intentionally left blank ...