7.21
Date Code 20081022
Instruction Manual
SEL-787 Relay
Communications
SEL ASCII Protocol and Commands
The information displayed for each GOOSE IED is described in the following
table.
Table 7.18
GOOSE Command Variants
Command Variant
Description
Access Level
GOOSE
Display GOOSE information.
1
GOOSE count
Display GOOSE information count times.
1
IED
Description
Transmit
GOOSE Control
Reference
This field represents the GOOSE control reference information that
includes the IED name, ldInst (Logical Device Instance), LN0
lnClass (Logical Node Class), and GSEControl name (GSE Control
Block Name) (e.g., SEL_787_1CFG/LLN0$GO$GooseDSet13).
Receive
GOOSE Control
Reference
This field represents the goCbRef (GOOSE Control Block
Reference) information that includes the iedName (IED name),
ldInst (Logical Device Instance), LN0 lnClass (Logical Node
Class), and cbName (GSE Control Block Name) (e.g.,
SEL_787_1CFG/LLN0$GO$GooseDSet13).
MultiCastAddr
(Multicast Address)
This hexadecimal field represents the GOOSE multicast address.
Ptag
This three-bit decimal field represents the priority tag value, where
spaces are used if the priority tag is unknown.
Vlan
This 12-bit decimal field represents the virtual LAN (Local Area
Network) value, where spaces are used if the virtual LAN is
unknown.
StNum
(State
Number)
This hexadecimal field represents the state number that increments
with each state change.
SqNum
(Sequence
Number)
This hexadecimal field represents the sequence number that
increments with each GOOSE message sent.
TTL
(Time to Live)
This field contains the time (in ms) before the next message is
expected.
Code
This text field contains warning or error condition text when
appropriate that is abbreviated as follows:
Transmit Data
Set Reference
This field represents the DataSetReference (Data Set Reference)
that includes the IED name, LN0 lnClass (Logical Node Class), and
GSEControl datSet (Data Set Name) (e.g.,
SEL_787_1/LLN0$DSet13).
Receive Data Set
Reference
This field represents the datSetRef (Data Set Reference) that
includes the iedName (IED name), ldInst (Logical Device
Instance), LN0 lnClass (Logical Node Class), and datSet (Data Set
Name) (e.g., SEL_787_1CFG/LLN0$DSet13).
Code Abbreviation
Explanation
OUT OF SEQUENC
Out of sequence error
CONF REV MISMA
Configuration Revision mismatch
NEED COMMISSIO
Needs Commissioning
TEST MODE
Test Mode
MSG CORRUPTED
Message Corrupted
TTL EXPIRED
Time to live expired
HOST DISABLED
Optional code for when the host is
disabled or becomes unresponsive after
the
GOOSE
command has been issued
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...