F.19
Date Code 20081022
Instruction Manual
SEL-787 Relay
IEC 61850 Communications
Logical Nodes
shows the LN associated with annunciation elements defined as
Logical Device ANN.
Table F.13
Logical Device: ANN (Annunciation)
Logical Node
Status
Relay Word Bit
Comment
Analog Quantities
MVGGIO12
AnIn01.mag to AnIn32.mag
Math Variables (MV01–MV32)
a
SCGGIO20
AnIn01.mag–AnIn32.mag
SELogic Counters (SC01–SC32)
b
AINCGGIO21
AnIn01.mag–AnIn04.mag
Analog Inputs (AI301–AI304)—Slot C
c
AINDGGIO22
AnIn01.mag–AnIn04.mag
Analog Inputs (AI401–AI404)—Slot D
AINEGGIO23
AnIn01.mag–AnIn04.mag
Analog Inputs (AI501–AI504)—Slot E
Relay Word Bits
INAGGIO1
Ind01.stVal–Ind02.stVal
Digital Inputs (IN101–IN102)—Slot A
OUTAGGIO2
Ind01.stVal–Ind03.stVal
Digital Outputs (OUT101–OUT103)—Slot A
SVGGIO3
Ind01.stVal–Ind32.stVal
SELogic Variables (SV01–SV32)
d
SVTGGIO4
Ind01.stVal–Ind32.stVal
SELogic Variable Timers (SV01T–SV32T)
LTGGIO5
Ind01.stVal–Ind32.stVal
Latch Bits (LT01–LT32)
e
TLEDGGIO6
Ind01.stVal–Ind08.stVal
Target LEDs (ENABLED, TRIP_LED, TLED_01–TLED_06)
PBLEDGGIO7
Ind01.stVal–Ind08.stVal
Pushbutton LEDs (PB1A_LED–PB4B_LED)
RMBAGGIO8
Ind01.stVal–Ind08.stVal
Receive MIRRORED BITS (RMB1A–RMB8A)
TMBAGGIO9
Ind01.stVal–Ind08.stVal
Transmit MIRRORED BITS (TMB1A–TMB8A)
RMBBGGIO10
Ind01.stVal–Ind08.stVal
Receive MIRRORED BITS (RMB1B–RMB8B)
TMBBGGIO11
Ind01.stVal–Ind08.stVal
Transmit MIRRORED BITS (TMB1B–TMB8B)
INCGGIO13
Ind01.stVal–Ind08.stVal
Digital Inputs (IN301–IN308)—Slot C
OUTCGGIO14
Ind01.stVal–Ind04.stVal
Digital Outputs (OUT301–OUT304)—Slot C
INDGGIO15
Ind01.stVal–Ind08.stVal
Digital Inputs (IN401–IN408)—Slot D
OUTDGGIO16
Ind01.stVal–Ind04.stVal
Digital Outputs (OUT401–OUT404)—Slot D
INEGGIO17
Ind01.stVal–Ind08.stVal
Digital Inputs (IN501–IN508)—Slot E
OUTEGGIO18
Ind01.stVal–Ind04.stVal
Digital Outputs (OUT501–OUT504)—Slot E
VBGGIO19
Ind001.stVal–Ind128.stVal
Virtual Bits (VB001–VB128)
a
Active data depends on the EMV setting.
b
Active data depends on the ESC setting.
c
Active data only if an I/O card is installed in the slot.
d
Active data depends on the ESV setting.
e
Active data depends on the ELT setting.
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...