4.108
SEL-787 Relay
Instruction Manual
Date Code 20081022
Protection and Logic Functions
Report Settings (SET R Command)
ALIAS1 = PB01 FP_AUX1 PICKUP DROPOUT
See
for the complete list of Relay Word bits. Use as many as
15 characters to define the alias, asserted text, and deasserted text strings. You
can use capital letters (A–Z), numbers (0–9), and the underscore character (_)
within each string. Do not attempt to use a space within a string because the
relay will interpret a space as the break between two strings. If you wish to
clear a string, simply type
NA
.
Event Report Settings
Event reports can be either 15 cycles or 64 cycles in length as determined by
the LER setting. For LER of 15, the prefault length, PRE, must be in the range
1–10. The relay can hold twenty-three 15-cycle event reports or seven
64-cycle event reports.
Load Profile Settings
Use the LDLIST setting to declare the analog quantities you want included in
the Load Profile Report. Enter up to 17 Analog Quantities, separated by
spaces or commas, into LDLIST setting. See
for a list of the available Analog Quantities. Also set the LDAR to the desired
acquisition rate for the report.
IMPORTANT:
All stored load data
are lost when changing the LDLIST.
Table 4.62
SET R SER Alias Settings
Setting
Prompt
Relay
Word Bit
Alias
Asserted
Text
Deasserted
Text
ALIAS1 :=
PB01
FP_LOCK
PICKUP
DROPOUT
ALIAS2 :=
PB02
FP_BRKR_SELECT
PICKUP
DROPOUT
ALIAS3 :=
PB03
FP_CLOSE
PICKUP
DROPOUT
ALIAS4 :=
PB04
FP_TRIP
PICKUP
DROPOUT
ALIAS5
–ALIAS20
NA
Table 4.63
Event Report Settings
Setting Prompt
Setting Range
Setting Name := Factory Default
EVENT TRIGGER
SEL
OGIC
ER := 0
EVENT LENGTH
15, 64 cyc
LER := 15
PREFAULT LENGTH
1–59 cyc
PRE := 5
NOTE:
Event report data stored in
the relay will be lost when you change
the LER setting, You must save the
data before changing the setting.
Table 4.64
Load Profile Settings
Setting Prompt
Setting Range
Setting Name :=
Factory Default
LDP LIST
NA, Up to 17 Analog Quantities
LDLIST :=NA
LDP ACQ RATE
5, 10, 15, 30, 60 min
LDAR := 15
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...