9.6
SEL-787 Relay
Instruction Manual
Date Code 20081022
Analyzing Events
Event Reporting
Use the front-panel
MAIN > Events > Display
menu to display event history
data on the SEL-787 front-panel display.
Use the
AC
SEL
ERATOR
QuickSet software to retrieve the relay event history.
View the
Relay Event History
dialog box via the
Analysis > Get Event Files
menu.
Clearing
Use the
HIS C
command to clear or reset history data from Access Levels 1
and higher. Clear/reset history data at any communications port. This will
clear all event summaries, history records, and reports.
Event Reports
The latest event reports are stored in nonvolatile memory. The 787 relay
captures the following types of data:
➤
Analog values
➤
Digital states of the protection and control elements, plus status
of digital output and input states
➤
Event Summary
➤
Settings in service at the time of event trigger, consisting of
Group, Logic, Global, and Report settings classes
The SEL-787 supports the following three separate event report types:
➤
Standard Analog Event Report (
EVE
command)
➤
Digital Event Report (
EVE D
command)
➤
Differential Event Report (
EVE DIFz
command, where z = 1,
2, or 3 for the three 87 elements)
Analog Event Reports (EVE Command)
The Analog Event Report includes:
➤
Analog values of Winding 1 and 2 currents; IAW, IBW, ICW,
IGW, (IGW only if voltage card is not used), neutral current IN
(if available), voltages and frequency (if voltage card is used)
➤
Digital states of the base model digital inputs (2) and digital
outputs (3)
➤
Event Summary
➤
Relay Settings
Filtered and Unfiltered Analog Event Reports
The SEL-787 samples the power system measurands (ac voltage and ac
current) 16 times per power system cycle. A digital filter extracts the
fundamental frequency component of the measurands. The relay operates on
the filtered values and reports these values in the standard, filtered event
report.
To view the raw inputs to the relay, select the unfiltered event report using the
EVE R
command. Use the unfiltered event reports to observe power system
conditions:
➤
Power system transients on current and voltage channels
➤
Decaying dc offset during fault conditions on current channels
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...