B.3
Date Code 20081022
Instruction Manual
SEL-787 Relay
Firmware Upgrade Instructions
Upgrade Instructions
c. Issue the
R_S
command to restore the factory default
settings.
The relay will then reboot with the factory default
settings.
d. Enter Access Level 2.
e. Restore relay settings back to the settings saved in
.
Step 11. Change the baud rate of the PC to match that of the relay prior
to
, and enter Access Level 2.
Step 12. Issue the
STATUS
command; verify all relay self-test results
are OK.
Step 13. Apply current and voltage signals to the relay.
Step 14. Issue the
METER
command; verify that the current and
voltage signals are correct.
Step 15. Autoconfigure the SEL-2032, SEL-2030, SEL- 2020 port if you
have a Communications Processor connected.
This step reestablishes automatic data collection between the
SEL-2032, SEL- 2030, SEL-2020 Communications Processor
and the SEL relay. Failure to perform this step can result in
automatic data collection failure when cycling communications
processor power.
The relay is now ready for your commissioning procedure.
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...