2.15
Date Code 20081022
Instruction Manual
SEL-787 Relay
Installation
Rear-Panel Connections
Power Connections
The
POWER
terminals on the rear panel (
A01 (+/H)
and
A02 (—/N)
) must connect
to 110–240 Vac, 110–250 Vdc, or 24–48 Vdc (see
for complete power input specifications). The
POWER
terminals are isolated
from chassis ground. Use 14 AWG (2.5 mm
2
) to 16 AWG (1.5 mm
2
) size wire
to connect to the
POWER
terminals.
For compliance with IEC 60947-1 and IEC 60947-3, place a suitable external
switch or circuit breaker in the power leads for the SEL-787; this device
should interrupt both the hot (+/H) and neutral (-/N) power leads. The
maximum current rating for the power disconnect circuit breaker or optional
overcurrent device (fuse) should be 20 A. Be sure to locate this device within
3.0 m (9.8 feet) of the relay.
Operational power is internally fused by a power supply fuse. See
for details. Be sure to use fuses that comply with
IEC 60127-2.
Grounding (Earthing)
Connections
You must connect the ground terminal labeled
GND
on the rear panel to a rack
frame or switchgear ground for proper safety and performance. Use 14 AWG
(2.5 mm
2
) wire less than 2 m (6.6 feet) in length for the ground connection.
Serial Ports
Because all ports (
F
,
2
,
3
, and
4
) are independent, you can communicate to any
combination simultaneously. Although serial
Port 4
on the optional
communications card consists of an EIA-485 (
4A
) and an EIA-232 (
4C
) port,
only one port is available at a time. Use the
Port 4
communications interface
COMMINF setting to select between EIA-485 and EIA-232.
The serial port EIA-485 plug-in connector accepts wire size AWG 24 through
AWG 12. Strip the wires 8 mm (0.31 inches) and install with a small slotted-
tip screwdriver. All EIA-232 ports accept 9-pin D-subminiature male
connectors.
For connecting devices at distances over 100 feet, where metallic cable is not
appropriate, SEL offers fiber-optic transceivers or the fiber-optic port. The
SEL-2800 family of transceivers provides fiber-optic links between devices
for electrical isolation and long-distance signal transmission. Contact SEL for
further information on these products.
IRIG-B Time-Code Input
The SEL-787 accepts a demodulated IRIG-B time signal to synchronize the
internal clock with an external source. SEL-787 relays with an EIA-485 serial
port option for
Port 3
have an external IRIG-B input at terminals
B01
and
B02
.
SEL-787 relays with an EIA-232 serial port option for
Port 3
have the IRIG-B
available in the EIA-232 port and can be connected to an SEL
communications processor. The available communications processors are the
SEL-2032, SEL-2030, SEL-2020, and the SEL-2100 Logic Processor.
Ethernet Port
The SEL-787 can be ordered with optional single/dual communications ports
of a 10/100BASE-T or 100BASE-FX Ethernet port. Connect to
Port 1
of the
device using a standard RJ-45 connector for the copper port and an LC
connector for the fiber-optic port.
Contact with instrument terminals can
cause electrical shock that can result
in injury or death.
!
DANGER
The relay contains devices sensitive to
Electrostatic Discharge (ESD). When
working on the relay with the front
panel removed, work surfaces and
personnel must be properly grounded
or equipment damage may result.
!
CAUTION
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...