2.17
Date Code 20081022
Instruction Manual
SEL-787 Relay
Installation
AC/DC Control Connection Diagrams
AC/DC Control Connection Diagrams
This section describes fail-safe versus nonfail-safe tripping, describes voltage
connections, and provides the ac and dc wiring diagrams.
Fail-Safe/Nonfail-Safe
Tripping
shows the output
OUT103
relay coil and Form C contact. When the
relay coil is de-energized, the contact between
A07
and
A08
is open while the
contact between
A07
and
A09
is closed.
Figure 2.14
Output OUT103 Relay Output Contact Configuration
The SEL-787 provides fail-safe and nonfail-safe trip modes (setting
selectable) for all output contacts. The following occurs in fail-safe mode:
➤
The relay coil is energized continuously if the SEL-787 is
powered and operational.
➤
When the SEL-787 generates a trip signal, the relay coil is de-
energized.
➤
The relay coil is also de-energized if the SEL-787 power supply
voltage is removed or if the SEL-787 fails (self-test status is
FAIL).
shows fail-safe and nonfail-safe wiring methods to control
breakers.
Figure 2.15
OUT103 Contact Fail-Safe and Nonfail-Safe Options
A07
A08
A09
Contacts shown with
OUT103 relay coil de-energized
OUT103
Relay Coil
Nonfail-safe
OUT103FS = N
52A
Breaker Trip Coil
TC
A08
A07
A07
TC
52A
Fail-Safe
(Electrically Held)
OUT103FS = Y
Circuit Breaker
Breaker Trip Coil
A09
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...