SEL-787 Relay
Protection and Logic Functions
Basic Protection
current problem. The process is now complete. The relay
receives the two settings as W1CTC = 12 and W2CTC = 7.
Winding Line-to-Line Voltages
Enter the nominal line-to-line transformer terminal voltages. If a load tap
changer is included in the transformer differential zone, assume that it is in the
neutral position. The setting units are kilovolts.
Current TAP
The relay uses a standard equation to set TAPn, based on settings entered for
the particular winding (
n
denotes the winding number.)
where:
The relay calculates TAP
n
with the following limitations:
➤
The tap settings are within the range 0.1 • I
NOMn
and
6.2 • I
NOMn
➤
The ratio TAP
MAX
/TAP
MIN
≤
7.5
Restrained Element Operating Current Pickup
The O87P setting range is 0.1 to 1.0; we suggest an O87P setting of 0.3. The
setting must be at a minimum for increased sensitivity but high enough to
avoid operation because of steady-state CT error and transformer excitation
current. The setting must also yield an operating current greater than or equal
to 0.1 • I
NOM
, when multiplied by the smallest of TAP1 and TAP2. Stated
another way,
O87P
MIN
≥
(0.1 • I
NOM
) / TAP
MIN
The above restriction applies to each winding sides (irrespective of TAP
magnitudes) when 1A and 5A nominal CTs are used in same relay.
Restraint Slope Percentage
Example:
The current transformer error, e, is equal to ±10 percent. In per unit:
e = 0.1
The voltage ratio variation of the power transformer load tap-changer, LTC, is
from 90 percent to 110 percent. In per unit:
a = 0.1
C = 1 if W
n
CT setting = Y (wye-connected CTs)
C =
if W
n
CT setting = D (delta-connected CTs)
MVA = maximum power transformer capacity setting (must be
the same for all TAP
n
calculations)
VWDG
n
= winding line-to-line voltage setting, in kV
CTR
n
= current transformer ratio setting
TAPn
MVA
1000
•
3
VWDG
CTR
n
•
•
------------------------------------------------------
C
•
=
3
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...