36
SEL-300G Relay
Quick-Start Guide
Date Code 20170804
Specifications
Type Tests
Frequency and Rotation
System Frequency:
60 or 50 Hz
Phase Rotation:
ABC or ACB
Frequency Tracking Range:
20–70 Hz
Note:
V
A
required for frequency tracking.
Communications Ports
EIA-232:
1 front and 2 rear
EIA-485:
1 rear
Baud rate:
300–38400
Time-Code Input
Relay accepts demodulated IRIG-B time-code input at Port 2.
Relay time is synchronized to within ±5 ms of time-source input.
Dimensions
See
for exact relay dimensions.
Operating Temperature
–40° to +85°C (–40° to +185°F)
Note:
LCD contrast impaired for temperatures below –20°C.
Weight
2U Rack Unit:
Minimum: 6.2 kg (13.5 lbs)
Maximum: 6.8 kg (15 lbs)
3U Rack Unit:
Minimum: 7.5 kg (16.5 lbs)
Maximum: 8.4 kg (18.5 lbs)
Type Tests
Cold:
IEC 60068-2-1:2007
Test Ad; 16 hr @ –40°C
Dry Heat:
IEC 60068-2-2:2007
Test Bd: 16 hr @ +85°C
Damp Heat, Cyclic:
IEC 60068-2-30:1980, Test Db; 25°
to 55°C, 6 cycles, 95% humidity
Dielectric Strength:
IEC 60255-5:2000, IEEE C37.90-
2005, 2500 Vac on analogs,
contact inputs, and contact
outputs; 3100 Vdc on power
supply; 2200 Vdc on EIA-485
communications port. Type tested
for 1 minute.
Impulse:
IEC 60255-5:2000, 0.5 J, 5000 V
Vibration:
IEC 60255-21-1:1988
[EN 60255-21-1:1995]
Class 2 Endurance, Class 2
Response
Shock and Bump:
IEC 60255-21-2:1988
[EN 60255-21-2:1995], Class 1
Shock Withstand, Class 2 Shock
Response
Seismic:
IEC 60255-21-3:1993
[EN 60255-21-3:1995], Class 2
1 MHz Burst Disturbance:
IEC 60255-22-1:1988, Class 3
(2500 V common and differential
mode)
Emissions:
IEC 60255-25:2000
Conducted Radio Frequency: ENV 50141:1993 10 V/m
IEC 61000-4-6:1996
[EN 61000-4-6:1996]
10 V/m, IEC 60255-22-6:2001 10
V/m
Digital Radio Telephone RF:
ENV 50204:1995 10 V/m at 900
MHz and 1.89 GHz
Electrostatic Discharge:
IEC 60255-22-2:2008
IEC 61000-4-2:2008
IEEE C37.90.3-2001
Severity Level:
Contact Discharge: ±2, 4, 6, and 8
kV
Air Discharge: ±2, 4, 8, and 15 kV
Radiated Radio Frequency:
ENV 50140:1993 10 V/m,
IEC 60255-22-3:2000 10 V/m,
IEC 61000-4-3:1998 10 V/m,
IEEE C37.90.2-1995 35 V/m, no
keying test, frequency elements
accurate to 0.1 Hz
Fast Transient Disturbance:
IEC 60255-22-4:2008
IEC 61000-4-4:2011
Severity Level:
Class A: ±4 kV, 5 kHz
±2 kV, 5 kHz on communication
s
ports
Object Penetration and Dust
Ingress:
IEC 60529:1989 [EN 60529:1992]
IP30
Protection Against Splashing
Water:
IEC 60529:1989 [EN 60529:1992]
IP54 from the front panel using the
SEL-9103
Surge Withstand:
IEC 60255-22-1:2007
Severity Level:
Common Mode: 2.5 kV on Power,
CT, PT, I/O
1.0 kV on Communications Ports
Differential Mode: 1.0 kV on
Power, PT, I/O
IEEE C37.90.1-2002
Severity Level:
Oscillatory: ± 2.5 kV, 1 MHz
common mode and differential
Fast Transient: ±4.0 kV, 2.5 kHz
common mode and differential
Generic Standard:
EN 50082-2:1995
Processing Specifications
AC Voltage and Current Inputs
16 samples per power system cycle, 3 dB low-pass filter cutoff
frequency of 560 Hz.
Digital Filtering
• One cycle cosine after low-pass analog filtering.
• Net filtering (analog plus digital) rejects dc and all harmonics
greater than the fundamental.
• Second-harmonic current and third-harmonic voltage filters are
also included for specific protection functions.
Protection and Control Processing
Four times per power system cycle for all elements except out-of-
step, loss-of-field, and RTD elements. Loss-of-field and out-of-
step elements are processed two times per power system cycle
and the RTD elements once in two seconds.
Relay Element Setting Ranges and Accuracies
Phase Distance Element (21)
5 A Model
Reach:
0.1–100.0 ohms
Offset:
0.0–10.0 ohms
Steady-State Impedance
Accuracy:
±5%, ±0.1 ohm
Minimum Phase Current:
0.5 A
Summary of Contents for SEL-300G
Page 1: ...20170804 SEL 300G Multifunction Generator Relay Quick Start Guide PM300GQS 01 ...
Page 4: ...This page intentionally left blank ...
Page 6: ...This page intentionally left blank ...
Page 8: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 55: ......
Page 56: ......