Operational Characteristics:
CME506
Cycle Times (minutes):
System Pressures (PSIG):
A -D Series Refrigerant Charge, R-404A
•
Air cooled:
32
ounces
•
Water cooled: 20 ounces
E Series Refrigerant Charge, R-404A
•
Air cooled: 23 ounces
•
Water cooled: 14 ounces
F Series Refrigerant Charge, R-404A
•
Air Cooled: 23 ounces
•
Water Cooled: 13 ounces
Typical Compressor Amps
•
Freeze: 10 - 11
•
Harvest:11 - 12
Typical Harvest Ice Weight
•
6.5 - 7 lb.
Water Cooled:
•
Discharge Pressure: 245 PSIG
•
Hi Pressure Cuts Out at: 450 PSIG
Fan Control Switch - for units so equipped:
•
Cut In: 240 PSIG + - 20 PSIG
•
Cut Out: 190 PSIG + - 10 PSIG
CME256, 506, 656, 806: AutoIQ™ Cubers
July 2002
Page 28
Air Cooled
70
o
F. indoor air, 50
o
F. water
90
o
F. indoor air, 70
o
F. water
Freeze
18 - 20
22 - 24
Harvest
2
1:30
Water Cooled
70
o
F. indoor air, 50
o
F. water
90
o
F. indoor air, 70
o
F. water
Freeze
20 - 22
22 - 24
Harvest
1.5 - 2.5
1.5 - 2
Air Cooled
70
o
F. indoor air, 50
o
F. water
90
o
F. indoor air, 70
o
F. water
Suction: End of Freeze
35- 37
35 - 37
Suction: Peak in Harvest
115 - 120
120 - 125
Discharge: 5 minutes into Freeze
240 - 260
240 - 260
Discharge: Minimum in Harvest
155- 165
165 - 175
Water Cooled
70
o
F. indoor air, 50
o
F. water
90
o
F. indoor air, 70
o
F. water
Suction: End of Freeze
30 - 34
30 - 34
Suction: Peak in Harvest
75 - 85
80 - 90
Discharge:
245 PSIG
245 PSIG
Discharge: Minimum in Harvest
150 - 160
175 - 185