EH330, EH430 and ECC Condensing Unit
Remote Low Side Cuber Service Manual
July 2013
Page 13
Tubing
The line set must be routed between the condensing unit and the ice maker’s location. During the transition
from quick connects to braze connections, the ice maker, condensing unit and line set may or may not have
quick connects, use this chart as a guideline for the proper action based on what is available at the site.
Condensing unit has sweat connections Condensing unit has quick connects
Ice making head has
sweat connections
If line set does not have quick connects,
route and use as is.
If line set has quick connects, recover
refrigerant from line set and cut all quick
connects off.
Compressor packs C1200CP,
C1410CP and C1800CP may be
connected to this head and will have
quick connects. If line set has quick
connects, recover refrigerant from line
set and cut one end of quick connects
off.
If line set does not have quick
connects, must use KTE6-EH stub kit
to add for condensing unit end.
Ice making head has
quick connects (prior
models of EH330 and
EH430)
If line set has quick connects, recover
refrigerant from line set and cut one end
of quick connects off.
If line set does not have quick connects,
must use KTE6-EH stub kit to add for ice
machine end.
If line set does not have quick
connects, must use KTE6-EH stub kit
to add for ice machine end.
Use the quick connects to make the
connection.
In all cases the line set will need to be shortened to fit.
Do NOT leave excess line set exposed outdoors,
especially on a roof.
Refrigerant Recovery and System Evacuation Notice
In the event the refrigerant must be recovered from this system and the system evacuated, recover and
evacuate from the three ball valve access valves.