Service Diagnosis - Optional Ice Level Controls
Vari-Smart (KVS)
Symptom
Probable Cause
Possible Correction
No ice, bin full light is ON
Adjustment knob set too low
Rotate knob to first position, knob’s
arrow pointing to the left of the L in
Lower (on the label)
Obstruction beneath sensor
Check for and clear any item that
might be below the sensor
Sensor recessed
Check sensor, sensor must
be flush in its holder and not
recessed.
No ice, b in code display, no bin
thermostat
Chute thermostat is open
Check chute thermostat
No ice, power light on, bin full light
is OFF
Photo-eye in chute blocked
Check controller display code. If a
b, check for blockage or scale build
up on photo eyes in chute
Check for photo eye failure
Optional Smart-Board is controlling
ice level
Check Smart-Board settings.
Ice level too high
Adjustment knob set to maximum
fill
Check if knob’s arrow points to
label arrow.
Sensor wire disconnected
Check for proper connection of
sensor wire to VS control board
Bin Thermostat
Symptom
Probable Cause
Possible Correction
No ice, b in code display
Bin stat is open
Check for ice on bin thermostat
capillary tube
Check for cold ambient in bin
Check continuity of bin thermostat
when capillary tube is warm,
replaced if does not close
Unit overfills, shuts off on photo-
eyes
Bin stat is stuck closed
Check position of bin thermostat
capillary tube.
Check continuity of bin thermostat
when ice is on the capillary tube,
replaced if does not open